6 INSTALLATION PLACE
1) Recommended installation height is 2.4-3.6 m.
2)
Detector should be installed on the ceiling
(or any other horizontal surface)
3) Alarm loop and power supply wires should
be located far from power cables.
To eliminate false alarm hazards
It is recommended to close all doors, air-vents,
switch off fans, air-conditioners and other
sources of intense air flows in the room during
protection
period.
Not recommended installation places
7 INSTALLATION PROCEDURE
1) Remove
cover
2) Remove
PCB
3) Install base
on the
ceiling
horizontally.
4) Install PCB
and perform
wiring (see
sec.8)
5)
Perform TEST-pass (see sec.9)
8 WIRING
Perform
accordance with control panel operating manual.
TMP – detector tampering control terminals;
RELAY – terminals for detector connection to
alarm loop;
+12V, GND – power supply terminals.
wiring
to
detector`s
terminals
9 TEST-PASS
1) Remove jumper from Mem plug, install
jumpers on Ind and Mode plugs.
2) Power detector ON. LED starts flash during
60 sec.
3) During this time
4) Close detector.
5)
To detect sensitive
zones
carry
out
TEST-pass
in the
secured zone with the
speed of 0,3
m/sec.
On
detection
(indicator is lighted
for 2sec) one should
stop,
mark
this
position, then make
step back and continue moving.
in
Repeat TEST-pass
inversely.
10 WARRANTY
The operation warranty period is 5 years from
the date of operation start-up but no longer than
5 years 6 months from the date of manufactur-
ing
subject to the requirements of Operating
Manual.