PLEASE READ THIS INSTALLATION MANUAL CAREFULLY BEFORE INSTALLING
THIS PRODUCT AND KEEP THIS MANUAL FOR FUTURE REFERENCE.
HIGH VOLTAGE WARNING:
Dangerous voltages are present within the power supply. Covers may only be removed
by qualified personnel when the power supply has been disconnected from the mains
supply voltage for more than 3 minutes. Covers must be replaced and all screws secured
properly before reconnecting to the mains voltage.
FUSING WARNING:
To ensure continued protection against risk of fire fuses must be replaced with the same
type and rating of fuse. Replacements should be carried out by qualified personnel only.
SPECIFICATIONS
INPUT ELECTRICAL – NEVO 600
Parameter
Details
AC Input Voltage
Nominally 100Vrms to 240Vrms
AC Input Frequency
DC Input Voltage
Standard
Medical
Power Rating
Input Current
600 watt output at 180Vrms
Fusing
Fast acting
NOTES:
1. NEVO 600 inputs can only be used with NEVO series output modules and must not be used for any other
purpose.
2. Use only a power source of the type indicated on the product label for the NEVO 600 inputs.
3. For installation relating to UL60601-1 (Medical) a suitable fuse as described above must be provided in line with
the Neutral inlet.
The NEVO 600 input module is supplied with an integrated fan. Ensure that the inlet and outlet ventilation holes
4.
are not obstructed. Ensure there is adequate ventilation provided in the enclosure wherein or near which the
power supply is mounted.
OUTPUT ELECTRICAL
Output
Vmin
Vnom
1
1.5V
5V
2
4.5V
12V
3
9V
24V
NOTES:
1. NEVO output modules can only be used with NEVO 600 input modules and must not be used for any other
purpose.
2. Take care when removing or adding output modules from the NEVO 600 input so that components are not
damaged in the process.
3. When the output voltage is adjusted upwards, the output current must be decreased proportionally so that the
unit does not exceed the Pmax average power rating as stated in the table above.
Peak power up to Ppk is available for not more than 5 seconds at a maximum of 50% duty cycle. The maximum
4.
rated average power must not be exceeded. Please refer to the full datasheet and user manual for more
information on using the Ppk feature.
ENVIRONMENTAL
Parameter
Details
Temperature
Humidity
Relative, non condensing
Altitude
Air Pressure
Full Power
Temperature
De-rate input and all outputs at 2.5% / °C
Humidity
Relative, non condensing
Altitude
Air Pressure
Noise Level
Measured 1m from fan
Shock
3000 bumps at 10G (16ms) half sine wave
Vibration
1.5G, 10 to 200Hz sine wave, 20G for 15min in 3 axes
Parameter
Details
Input to Output
Isolation
Input to Chassis
Voltage
Output to Chassis
Output to Output
Isolation
Primary to Secondary(Reinforced)
Clearance
Primary to Chassis (Basic)
Isolation
Primary to Secondary(Reinforced)
Creepage
Primary to Chassis (Basic)
Standard: 250Vac, 60Hz, 25 °C
Leakage
Current
Medical: 250Vac, 60Hz, 25 °C
GENERAL INSTALLATION
Parameter
Details
Equipment class
I
Installation category
II
Pollution degree
2
Material group
IIIb (indoor use only)
MECHANICAL
Parameter
Details
Size
77.7mm x 129.7mm x 41.0mm
(all external dimensions ± 1.0mm)
Weight
360 grams + 60 grams per output module
Mounting
Bottom or Side mounting (See diagram details)
WARNINGS
Min
Max
85
264
47
63
120
370
120
300
600
4.5
5
Vmax
Imax
Pmax
7.5V
25A
125W
15V
15A
150W
30V
7.5A
150W
Min
Max
-40
85
5
95
-200
5000
54
106
-20
50
50
70
5
95
-200
3000
78
106
45
SAFETY
Min
Max
4000
1500
250
250
7
2.5
12
4
1500
300
Parameter
Details
Flammability rating
94V-2
IP Rating
IP 10
RoHS Compliance
Yes
This power supply is intended for use within equipment or enclosures which restricts access to
authorized personnel only. The instructions in this manual and all warning labels on the product must
be followed carefully.
SAFETY
The NEVO 600S is designed in accordance with safety requirements for UL60950-1, EN60950-1,
IEC60950-1, CSA22.2 no. 60950-1 and LV Directive 2006/95/EC.
The NEVO 600M is designed in accordance with safety requirements for UL60601-1, EN60601-1,
EN61010-1, IEC60601-1, IEC61010-1, CSA22.2 no 601-1 and LV Directive 2006/95/EC.
All power supplies must be installed correctly in a controlled environment which restricts access to any
unauthorized personnel. Equipment and system manufacturers must protect service personnel against
unintentional contact with the output terminals.
DERATINGS
Temperature - Input and output power must be de-rated by 2.5%/°C above 50°C.
Input Voltage - Input and output power must be de-rated by 0.55% / Vrms below 180Vrms (402W @
120Vrms, 303W @ 90Vrms)
Always remember to take the appropriate deratings into consideration before specifying any power
supply for an application.
Units
V rms
HAZZARDS
Hz
V dc
If series and/or parallel combinations of outputs exceed safe voltage and/or energy levels, the final
equipment manufacturer must provide appropriate protection for both users and service personnel.
Watts
Amps
HEALTH AND SAFETY
Amps
To comply with section 6 of the health and safety at work act, a label that is clearly visible to service
personnel must be placed on the final equipment, which warns that surfaces of the power supply may
be hot and should not be touched when the product is operating.
FUSING
The power supply has internal single pole fusing in the L (Live) line.
SERVICING
The power supply contains no user serviceable parts. Repairs must be carried out by authorised
personnel only.
Ppk
(4)
187.5W
APPROVAL LIMITATIONS – NORTH AMERICA
(4)
225W
When this product is used with 180VAC–253VAC mains where no neutral is present, connect the two
(4)
225W
live wires to L (Live) and N (Neutral) on the input connector.
COOLING
For proper cooling of the power supply, the air intake and outlet must not be impeded. Allow 50mm
clearance at both ends and position cabling appropriately.
EARTH TERMINAL MARKING
To comply with the requirements of UL60950-1, EN60950-1, IEC60950-1, CSA22.2 no. 60950-1,
UL60601-1, EN60601-1, EN61010-1, IEC60601-1, IEC61010-1, CSA22.2 no 601-1 where the incoming
wiring earth is intended for connection as the main protective earth conductor and where the
terminals for such a connection is not supplied on a component or subassembly such as a terminal
block, the user shall add an appropriate label displaying a protective earth symbol in accordance with
Units
60417-2-IEC-5019 directly adjacent to the terminal. The label should be durable and legible and should
°C
withstand the 15s rub test as per UL60950-1 section 1.7.15.
%
WARRANTY
Meters
K Pa
Contact your sales agent or Vox Power for product repairs. See Vox Power standard terms and
°C
conditions for warranty conditions.
°C
PRODUCT LABELS
%
NEVO 600M and NEVO 600S
Meters
K Pa
The external product label contains information relevant to the power system. The label contains
d BA
input voltage, maximum input current, input frequency, maximum output power, fuse rating and type,
serial number, approvals and product part number in format NEVO 600o-oooo-ooo.
NEVO OUTPUT MODULES
Each output module label contains information relevant to that particular output. The label contains
voltage adjustment range, maximum output current, serial number, approvals and part number in
Units
format OP.
V ac
V ac
OTHER
V dc
A label warning that external surfaces are hot during operation and that the unit should be allowed
V dc
to cool down properly should be placed on the unit where such a label is clearly visible.
mm
The NEVO 600 range is designed to comply with EMC standards but it does not imply that the end
mm
system will comply.
mm
To prolong the life of the unit use in dust free environment.
mm
Units can be damaged during transit. Contact your sales agent or Vox Power and DO NOT apply
u A
u A
power to the unit in case of transit damage
Always use adequately sized cables and ensure good crimp connections. Use cable supports to
minimise stress on connectors.
Avoid excessive shock or vibration.
NEVO 600S/M SERIES
Installation Manual
IMPORTANT INSTALLATION NOTES