Summary of Contents for ICT PRT-CTRL-DIN

  • Page 1 PRT-CTRL-DIN Protege GX DIN Rail Integrated System Controller Installation Manual...
  • Page 2 Copyright © Integrated Control Technology Limited 2003-2021. All rights reserved. Last Published: 25-May-21 4:27 PM PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 3: Table Of Contents

    Magnetic Reader Connection Door Contact Connection Lock Output Connection Programming the Onboard Reader Inputs EOL Resistor Value Options Duplex Inputs Trouble Inputs Outputs Bell/Siren Output Relay Outputs Reader Outputs PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 4 Repair Database Compatibility Windows Firewall Multiple Firewalls Encryption Disabling Encryption Telnet Hardware Configuration Setting the IP Address from a Keypad Temporarily Defaulting the IP Address Defaulting a Controller PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 5 Central Station Signal Receiver Compatibility List UL Operation Mode ULC Compliance Requirements CAN/ULC-S304 CAN/ULC-S319 CAN/ULC-S559 UL Compliance Requirements UL1610 UL294 FCC Compliance Statements Industry Canada Statement Disclaimer and Warranty PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 6: Introduction

    NIST Certified AES 128, 192 and 256 Bit Encryption ⦁ Factory loaded HTTPS certificate ⦁ OSDP configurable RS-485 ⦁ 8 high security monitored inputs ⦁ Built-in offsite communications dialer (ContactID or SIA) ⦁ Industry standard DIN rail mounting PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 7: Installation Requirements

    The National Electrical Code, ANSI/NFPA 70 ⦁ The Canadian Electrical Code, Part I, CSA C22.1 ⦁ AS/NZS 2201.1 Intruder Alarm Systems ⦁ The Local Authority Having Jurisdiction (AHJ) ⦁ PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 8: Grounding Requirements

    (RS-485 N+, N-, NA, NB) DIN Rail Enclosure Additional DIN Rail Enclosure(s) Controller Reader Expander Dialer’s Earth Ground Connection Input Expander Power Supply Output Expander AC Mains Wiring Earth Ground Link Connection PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 9 Sector or Building #3 Note that the DIN rail enclosure earth terminal is connected to the power supply V- terminal. There must be only one single earth grounding point per system. PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 10: Mounting

    A Protege DIN rail module can be removed from the DIN rail mount using the following steps: Insert a flat blade screwdriver into the hole in the module tab clip. Lever the tab outwards and rotate the unit off the DIN rail mount. PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 11: Wiring Diagram

    Input is in the TAMPERED state the Controller Installation Manual for instructions it's IP address. on programming the onboard reader. Flashing green Input is in the SHORTED state PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 12: Connections

    A battery backup must be connected to the module network to provide a monitored supply. The battery plays an important role in power conditioning and provides a continuous source of power in the event of a power outage. Example 2A Power Supply Connection: PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 13 When using multiple power supplies it is important to ensure that all ground connections (V-) are connected between all power supplies and that no power connections (V+) are connected between any power supplies. PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 14: Auxiliary Outputs

    CAT5e / CAT6 are also supported for data transmission when using ground in the same cable (to a ⦁ maximum length of 100m (328ft)) Warning: Unused wires in the cable must not be used to carry power to other devices. PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 15: End Of Line (Eol) Resistors

    2400bps modem. The telephone line can be connected directly to the controller using the onboard telephone connection terminals. Telco line tip and ring input Telco line out PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 16: Ethernet 10/100 Network Interface

    UL and ULC standard requirements associated with a signal receiving center. ⦁ The controller must be installed in the same room as the network equipment that provides it the network connection. PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 17: Door Access Control

    The shield connection must only be connected at one end of the cable in the metallic enclosure (frame ⦁ grounded). All UL listed ICT readers are shipped with single LED mode set as default and are fully compatible with the Protege system, such as tSec Standard Readers, tSec Mini Readers, etc. Wiegand Reader Connection The controller allows the connection of 2 magnetic clock and data reading devices or 4 Wiegand reading devices and the ability to control 2 doors (entry or exit only) or 1 door (entry and exit).
  • Page 18: Multiple Wiegand Reader Connection

    Location Configuration Entry Green and orange wires not connected. Exit Green and orange wires connected together. PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 19: Rs-485 Reader Connection (Entry Only)

    The controller allows the connection of standard magnetic track 2 format cards and provision is made in the software for a large number of formats. Formats include BIN number for ATM access control and first 4, 5 and 6 card numbers. PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...
  • Page 20: Door Contact Connection

    The following example shows the connection of a normally closed door position monitoring contact to monitor the open, closed, forced and alarm conditions of the door. PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual...