Speed selection tables
In order to select the correct step for the supply and return fan it is necessary to:
- Choose the table whose unit size number corresponds to the size indicated in the AED unit selection software report.
- Identify the steps of the supply/return fan, choosing from column H (high), the steps in which the RPM values are
closest to those indicated in the AED unit selection software report for the aforementioned fan.
- Set the values of the selected steps on the controller by going to the Service settings  Field settings path and
proceed with the following settings
a. 19(29)-2- Step_selected_ supply_fan, for the Step of the supply fan, from 01 to 15
b. 19(29)-3- Step_selected_return_fan, for the return fan Step, from 01 to 15
- If the RPM values for the supply and return fans are not present in column H but in column UH (very high), then:
- Set the initial fan speed to Very High by going to the Service Settings  Field settings path and changing the
default value from 17(27)-4-01(High) to17(27)-4-02(Very high)
- Set the selection steps as indicated in step 3.
Heat recovery operation
Step
UH
(very
high)
01
2164
02
2227
03
2290
04
2350
05
2409
Fan RPM
setting SA
06
2469
(19(29)-2-...)
07
2529
08
2586
09
2654
Fan RPM
10
2728
setting EA
(19(29)-3-...)
11
2796
12
2868
13
2931
14
2999
15
3059
The table refers to the indicated values, subject to tolerances.
To adjust the desired air flow value based on on-site measurements, you can increase the RPM to increase
the flow and decrease the RPM to reduce it. If necessary, slightly modify the fan speed in order to obtain
the desired air flow.
Supply fan
Bypass operation
H
L (low)
UH
(high)
1803
951
2264
1868
1025
2324
1939
1099
2384
2005
1176
2443
2071
1253
2503
2127
1327
2566
2187
1404
2626
2245
1475
2685
2310
1555
2754
2367
1634
2825
2416
1709
2894
2472
1783
2965
2524
1848
3033
2583
1919
3104
2632
1985
3170
Modular T Smart Size 03
Heat recovery operation
H
L
UH
1828
1028
2390
1908
1093
2439
1982
1162
2492
2048
1225
2541
2122
1290
2593
2187
1359
2642
2261
1423
2695
2327
1489
2744
2401
1572
2806
2469
1657
2873
2521
1734
2932
2577
1817
2997
2629
1891
3054
2685
1957
3113
2737
2016
3170
Return fan
By-pass operation
H
L
UH
2036
1282
2145
2095
1345
2202
2159
1409
2259
2217
1474
2316
2276
1541
2370
2323
1602
2425
2375
1666
2476
2422
1731
2531
2479
1800
2593
2529
1865
2657
2573
1925
2717
2626
1988
2781
2670
2048
2841
2721
2115
2908
2763
2172
2964
H
L
1763
951
1818
1008
1877
1065
1932
1122
1992
1178
2046
1236
2105
1293
2157
1352
2219
1424
2279
1499
2330
1565
2380
1640
2427
1706
2476
1775
2524
1828