(Optional) Replacing Condensate P
ump
Copyright © 2017 Huawei Technologies Co., Ltd. All rights reserved.
Step 1 Turn of all AC input switches;
Step 2 Open the rear door;
Step 3 Remove the air f lters;
Step 4 Remove the condensate pump, as
shown in Figure;
Step 5 Install a new condensate pump
and connect cables in a reverse order;
Step 6 Install the air f lters;
Step 7 Close and lock the rear door;
Step 8 Tap Maint > Performance
Maint on the home screen and clear the
condensate pump total runtime.