Trane X13511542010 User Manual page 22

Communicating thermostat for heat pump control bacnet ms/tp version
Table of Contents

Advertisement

Installer Configuration Parameter Menu
Configuration
Significance
parameters
Default value
Minimum on/off
operation time for
stages
Default value = 2
minutes
Anti-short cycling can
be set to 0 minutes for
Anticycle
equipment that posses
their own anti cycling
timer. Do not use that
value unless the
equipment is equipped
with such internal timer.
Failure to do so can
damage the equipment.
Heating stages cycles
per hour
Default value = 4 C.P.H.
For multi stage models,
Heat cph
heat cph applies to W1
and W2
For heat pump models,
heat cph applies to W1
only (Emergency heat)
Cooling stages cycles
per hour
Default value = 4 C.P.H.
For multi stage models,
cool cph applies to Y1
and Y2
cool cph
For heat pump models,
cool cph applies to Y1
and Y2 in cooling and
heating independently
of the reversing valve
position
Minimum deadband
Deadband
Default value = 2.0°F
(1.1°C)
Fan control
Default value = On
For multi stage models,
fan control applies to
fan cont
W1 and W2
For heat pump models,
fan control applies to
W1 only (Emergency
heat)
Fan delay
fan del
Default value = Off
Temporary occupancy
ToccTime
time
Default value = 3 hours
Room air temperature
sensor calibration
cal RS
Default value = 0.0°F or
°C
22
Minimum On/Off operation time of cooling and heating stages.
Important:
Anti-short cycling can be set to 0 minutes for equipment that posses their own anti
cycling timer. Do not use this value unless the equipment is equipped with such
internal timer. Failure to do so can damage the equipment.
0, 1, 2, 3, 4 and 5 minutes
Will set the maximum number of heating stage cycles per hour under normal control operation. It
represents the maximum number of cycles that the equipment will turn ON and OFF in one hour.
Note that a higher C.P.H will represent a higher accuracy of control at the expense of wearing
mechanical components faster.
3, 4, 5, 6, 7 and 8 C.P.H.
Will set the maximum number of cooling stage cycles per hour under normal control operation. It
represents the maximum number of cycles that the equipment will turned on and off in one hour.
Note that a higher C.P.H will represent a higher accuracy of control at the expense of wearing
mechanical components faster.
3 or 4 C.P.H.
Minimum deadband value between the heating and cooling setpoints. If modified, it will be applied only
when any of the setpoints are modified.
2, 3 or 4°F (1.0 to 2.0°C)
Fan control in heating mode.
When selecting On; the thermostat in all cases will always control the fan (terminal G).
Valid for On or Auto fan mode
When selecting Off; the fan (terminal G), when heating stages (terminals W1 and W2) are solicited,
will not be energized. The fan in this case will be controlled by the equipment fan limit control.
Valid only for Auto fan mode. On fan mode will leave the fan always on.
On or Off
Fan delay extends fan operation by 60 seconds after the call for heating or cooling ends.
Valid only for Auto fan mode. "On" fan mode will leave the fan always on.
Off or On
Temporary occupancy time with occupied mode setpoints when override function is enabled When the
thermostat is in unoccupied mode, function is enabled with either the menu or DI1 or DI2 configured
as remote override input.
0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 and 12 hours
Offset that can be added/subtracted to actual displayed room temperature
± 5.0°F (± 2.5°C)
Adjustments
BAS-SVU10C-EN