Emerson Fisher FIELDVUE DVC6005 Series Instruction Manual Supplement page 9

Remote mount digital valve controllers
Hide thumbs Also See for Fisher FIELDVUE DVC6005 Series:

Advertisement

Instruction Manual Supplement
D104211X012
Figure 4. ATEX Loop Schematics FIELDVUE DVC6005f and DVC6015, DVC6025, DVC6035; FISCO Installations
ATEX APPROVED
FISCO DEVICE
NOTE 2, 3
ATEX APPROVED
FISCO TERMINATOR
ZONE 0, Ex ia IIC
TYPE
T CODE
---
T4
DVC6015
DVC6025
T5
DVC6035
T6
1 SEE NOTES IN FIGURE 5
GE60771 Sheet 13, Rev. D
ZONE 0, Ex ia IIC
ZONE 20, Ex ia IIIC
DVC6015, DVC6025
DVC6035
Ui = 30 VDC
Ii = 100 mA
Ci = 0 uF
Li = 0 mH
Pi = 160 mW
NOTE 2, 3
1
1
ZONE 20, Ex ia IIIC
MAX
SURFACE
T AMB
TEMP
T AMB
≤ 125_C
T146_C
---
T135_C
≤ 114_C
≤ 125_C
≤ 79_C
T100_C
≤ 95_C
≤ 64_C
T85_C
≤ 80_C
HAZARDOUS LOCATION
ZONE 0, Ex ia IIC
ZONE 20, Ex ia IIIC
DVC6005F
REMOTE
FIELD WIRING
FIELD WIRING
TERMINAL BOX
TERMINAL BOX
LOOP
POT
TERMINALS
30K OHMS
Uo = 17.5 VDC
Ui = 17.5 VDC
Io = 17.5 mA
Ii = 380 mA
Po =105 mW
Pi = 5.32 W
Co = 121 nF
Ci = 5 nF
Lo = 100 mH
Li = 0 mH
TYPE
DVC6005F
DVC6005 Digital Valve Controllers
NON‐HAZARDOUS LOCATION
ATEX APPROVED
FISCO BARRIER
NOTE 2, 3, 4
ZONE 0, Ex ia IIC
ZONE 20, Ex ia IIIC
MAX
SURFACE
T CODE
T AMB
TEMP
T4
≤ 80_C
T103_C
T5
≤ 77_C
T100_C
T6
≤ 62_C
T85_C
August 2017
1
T AMB
≤ 80_C
≤ 77_C
≤ 62_C
9