Page 2
Introduction of the Cleaning On message during periodic cleaning phase Configuration 11 has been added Boiler probe thermostat maximum range increased, NTC 231K probe added 20/04/2018 Automatic Extinguishing function modified Door management modified Pag. 2 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Introduction The MB250 Controller is a device to manage stoves and boilers with automatic ignition and pellet loading. The operation of the heating system is determined by reading the exhaust temperature, water temperature, and through the acquisition of the parameters setup by the user. The parameters of the controller are fully configurable inside the menu.
Make connection in a tidy way; keep separated cables of low voltage (probes, contacts, control panel flat) and cables of high voltage (power source, loads) to reduce interference problems Pag. 6 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 8
51-52-54 Encoder Sensor (see parameter A57) 52: signal 54: +5V Local Keyboard Connection RS232 Serial Port Connection Serial Port RS232 RS485 Serial Port Connection Serial Port RS485 Connect to the Earth CONNECT ALWAYS Pag. 8 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 11
√ √ – – Bottom Buffer probe √ √ √ – – NOTE If a contact is connected on input IN10, it has to be connect to pins 50 and 53. Pag. 11 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 12
Links Below is shown how connect the Remote Keyboard to the SYPlug02 board that leads out of the stove or boiler the control board’s RS232 and RS485 connectors. Pag. 12 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
If the door is open, the Timer resets. In case in which the sensor is selected but not used, short circuit the corresponding pins of the board. Pellet Thermostat Pag. 13 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
If A01=1, 2, 3, 4, 5, 6, 7 and the input is not used short circuit the relative pins. Pellet Level Setting the parameters P36, in the Technical Menu it is possible to: P44, different from 2 Pag. 14 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
NOTE: even if the sensor can read temperatures in the range 0 ÷ 500 °C the entire sensor wiring can work only in the range 0 ÷ 500 °C. TiEmme elettronica is not responsible of any damage or bad functioning of the probe due to a wrong use of it (i.e. thermic and mechanical stresses to the probe).
If A13=2, on Summer all operations of Room Thermostat are disabled except for A01=0. If A01=1, 2, 3, 4, 5, 6, 7 and the input is not used short circuit the relative pins. Pag. 17 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Enter in User Menu 1/submenu, Enter in User Menu 2 (push for 3 seconds), Save data Enter in Visualizations Menu, Increase Enter in Visualizations Menu, Decrease Function Function Room Thermostat reached External Chrono reached Winter Summer Pellet Modality/Wood Modality Combi Modality On Pag. 18 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
The arrow in the main screen allows to access the toolbar where the system special led are located. The followings are available: combustion power set Chrono state Winter Summer Wood Pellet System functioning Climatic function Pag. 19 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Minimum air flow in Check Up is not reached Er42 Maximum air flow exceeded (F40) Er47 Error Encoder Auger: missing signal Encoder (if P81=1 or 2) Er48 Error Encoder Auger: Auger regulation speed not achieved (if P81=1 or 2) Pag. 20 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 21
Remaining hours before the system performs the stove cleaning; it is displayed if Cleaning is greater then 0. Working Hours Working Hours of the stove in Run Mode, Modulation and Safety Ignitions Number of Ignition Attempts Product Code Product Code 549 Pag. 21 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Combustion Fan Menu. This menu is visible only if is different from 1 and e A64=1. Example: P16=5%, Step= +3 Default U03=1000 U04=1200 U05=1400 U06=1600 U07=1800 U11=900 Values Calibrated U03=1150 U04=1380 U05=1610 U06=1840 U07=2070 U11=1030 Values Pag. 22 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 23
Menu to manage the Mixer Valve. It is possible to regulate it in automatic mode (see section 7.13.14) or force it to open or close (both for a time twice the parameter T82). It is visible only if P26=7, 8. Pag. 23 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 24
Cleaning Reset * This menu allows to reset the message of Function System Maintenance 2. It is visible only if T67>0. Chrono Menu to select the Chrono’s program modality and the timers of Ignition/Extinguishing of (for LCD100 and the stove. Pag. 24 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 25
00:00 00:00 Weekly The programs are the same for all days of the week. Week-end Mon-Fri___________ Choose between 'Monday-Friday' and 'Saturday-Sunday' Sat-Sun and then set the switching on and off times. Pag. 25 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Menu to enter into technical menu. The access is protected by password ( System Menu * password: 0000 ). See chapter 8 for more details. * only for local keyboard ** only for LCD keyboard *** only for K400 keyboard Pag. 26 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Extinguishing with error message Er01. If A27=1 and the boiler water temperature exceeds the Boiler Thermostat Th24, in Extinguishing and Recovery Ignition the augers and the fans are disabled. Pag. 27 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Preheating Combustion Timer Control Thermostats Heating Resistance Auger P71≠4 and exhaust temp.>Th09 Thermostat goes in Run Mode P74,P75,P76≠18 P71=4 or Light flame > Thermostat goes in Run Mode P74,P75,P76=18 Pag. 28 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 29
Retry Ignition from the Variable P71=4 or Phase; in case of ignition attempts P74,P75,P76=18 At the end of if light flame < Thermostat are over, it goes in Extinguishing with alarm Er12 Pag. 29 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Combustion Heating Timer Control Thermostats Auger Resistance This phase is realized only if an output is set as Brazier Cleaning Engine; it ends when (Maximum the engine stops Speed if A67=1) Pag. 30 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
P74,P75,P76=18 at the end of timer if light flame < Thermostat Extinguishing with alarm Er03 System with Exhaust temp > Th08 thermostat Thermocouple goes in Safety Water temp.> Th25 thermostat Pag. 31 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
P74,P75,P76=18 at the end of timer if light flame < Thermostat Extinguishing with alarm Er03 System with Exhaust temp. > Th08 thermostat Thermocouple goes in Safety water temp.>Th25 thermostat Pag. 32 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
P71≠4 At the end of timer if exhaust temp.>Th28 wait thermostat Light flame > Thermostat starts timer P71=4 At the end of if light flame > Thermostat wait Pag. 33 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 34
Extinguishing of the combustion for the time. At the end start the Work phase Work Combustion Heating Timer Control Thermostats Resistance Auger Combustion on for the time. At the end start the Pause phase Pag. 34 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Combustion Heating Timer Control Thermostats Auger Resistance This phase is realized only if an output is set as Brazier Cleaning Engine; it ends (Maximum Speed when the engine stops. if A67=1) Pag. 35 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Wood Run Mode If the exhaust temperature is lower than Th13 thermostat, starts the timer: if the temperature rises above this thermostat, the timer is reset, otherwise the system returns to Off state. Pag. 36 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
** If the Bottom Buffer Probe is present, the buffer charge ends when both the Buffer Thermostats, Th58 and Th85, are satisfied. Charging resumes if buffer temperature < (Buffer Thermostat Th58 - Ih58-1) Pag. 37 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Wood mode, otherwise it keeps working with Pellet. Here the system keeps checking the Th68 thermostat for the transition to Wood. Pag. 40 / 70 DMAN802000093-Manuale MB250 Idro Legna-Pellet STD11...
Page 41
Pellet. When T71 expires, working power is no more fixed, while Th68 thermostat is still monitored. For the Th68 thermostat control, the opening / closing of the door can take place both in Wood or Pellets phase. Pag. 41 / 70 DMAN802000093-Manuale MB250 Idro Legna-Pellet STD11...
P86=1 goes in Block. To unblock the system, or if P86=0 to disappear the message ' ', it is necessary to reset the counter in the menu ‘Reset Service’. To disable this feature set T66=0, to enable it set T66>0. Pag. 42 / 70 DMAN802000093-Manuale MB250 Idro Legna-Pellet STD11...
If the Combustion Fan was off, it is turned on at the speed U12, otherwise it continues to work on the power to which it was working. If the fuel in the tank is run out, the function is disabled. Pag. 43 / 70 DMAN802000093-Manuale MB250 Idro Legna-Pellet STD11...
This phase lasts T100 seconds: During this time the motor is off and must have repositioned Phase 2 itself in the starting position. At the end the system moves to Phase 3. Pag. 44 / 70 DMAN802000093-Manuale MB250 Idro Legna-Pellet STD11...
Run Mode and Modulation, when the work time exceeds the value of the parameter T76, the cleaning starts while the combustion parameters remain the same. The cleaning is repeated for Pag. 45 / 70 DMAN802000093-Manuale MB250 Idro Legna-Pellet STD11...
Th15. If the door opens or any error occurs, the output is switched off. Air Valve 2 The output is ON in Pellet modality if Combustion Fan is on (except in the Ignition state in Preheating, Preload and Fixed phases). Pag. 46 / 70 DMAN802000093-Manuale MB250 Idro Legna-Pellet STD11...
The Mixer Valve is available only if P26=7, 8, 9. The management involves the use of two outputs Aux3 and Aux1. The electrical connections and the plumbing plants in which it is enabled are the following: P2-3 P2-3 Pag. 47 / 70 DMAN802000093-Manuale MB250 Idro Legna-Pellet STD11...
To disable the cleaning in this phase set P51=0 Periodically, during the time TM41÷TM48, when the operating time in Run Mode, Modulation and Standby-Maintenance (A27=1) is greater than parameter. The combustion parameters don’t Pag. 48 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 49
If during the normal operation the thermo-regulator reads the limit switch as open, the Brazier Engine is activated in BACKWARD mode to try to close the contact; if it cannot do it within the TM11 time, the system goes in Block state with the error message Er25. Pag. 49 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Estimating the air flow speed of the inlet it can adjust the scope of the system. It works in Run Mode and Modulation states in Pellet modality. For the correct use of the system do the following: Pag. 50 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 51
5. If on keyboard display appears the message Er39 the device is damaged, the regulation is disabled and the outputs, Auger and Fan, will work with the factory settings Pag. 51 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
: Th18=5 °C, Th19=40 °C, Th20=30 °C, Th21=70 °C Water Temperature Flow Switch Modality Functioning P2 Valve P1 Pump T < 5°C Heat. (OFF) 5°C ≤ T< 30°C Heat. (OFF) 30°C ≤ T< 40°C (ON) Pag. 52 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 53
If A41=1 and the system is in Off state, the P1 Pump is off if there isn’t a sanitary water demand and if the water temperature in the boiler is greater than Th18 and lower than Th21 thermostat. Pag. 53 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 55
To avoid freezing, the Pump is On if the water temperature is below the thermostat Th18. If the water temperature exceeds the value of the Th21 thermostat for safety reasons the Pump is always on. Sanitary Plant When there is a sanitary water demand the system stops the Pump. Pag. 55 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 56
If A41=1 and the system is in Off state, the P1 Pump is off if the water temperature in the boiler is greater than Th18 and lower than Th21 thermostat. Heating This plant manage the Mixer Valve to adjust the return temperature. (see sec. 7.13.14). Pag. 56 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 57
If A41=1 and the system is in Off state, the P1 Pump is off if the water temperature in the boiler is greater than Th18 and lower than Th21 thermostat. Heating This plant manage the Mixer Valve to adjust the return temperature. (see sec. 7.13.14). Pag. 57 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 58
T < 75°C T ≥ 70°C T < 65°C DHW (ON) T < 70°C Heat. T < 75°C T ≥ 65°C (OFF) T ≥ 70°C Heat. T ≥ 75°C T ≥ 65°C (OFF) Pag. 58 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 59
T < 75°C T ≥ 70°C T < 65°C DHW (ON) T < 75°C T < 70°C T ≥ 65°C heat. (OFF) T ≥ 75°C T ≥ 70°C T ≥ 65°C heat. (OFF) Pag. 59 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Code Description Unit V01* Ignition Power (only in Pellet modality) [RPM] V02* Stabilization Power (only in Pellet modality) [RPM] V03* Power 1 [RPM] V04* Power 2 [RPM] V05* Power 3 Pag. 61 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
High Voltage 2 (Pressure switch) delay Exit from Standby delay Minimum period time of extinguishing Waiting time pre-extinguishing for no flame Waiting time pre-extinguishing in Safety Final cleaning time Delay time combustion power change Pag. 64 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 65
Length of the extinguishing phase in Ignition Recover in case of ‘Automatic TM18 Switch off’ function if A40=2 TM41 Brazier Cleaning Engine work time if P44, or P36=25 in Run Mode 9600 Pag. 65 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
0=the system does not go into Standby; 1=the [nr] system goes into Standby Enabling Buffer Thermostat in Wood Modality [nr] Enabling Er02 management in Wood Modality [nr] Pag. 66 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Page 67
Input IN2 management (pin 27-28: see section 3.1) [nr] Input IN3 management (pin 29-30: see section 3.1) [nr] Input IN5 management (pin 33-34-35: see section 3.1) [nr] Number of cleaning cycles for Cleaning Engine 2 [nr] Pag. 67 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Waiting time for stabilization of regulation of first output Waiting time for stabilization of regulation of second output Waiting time for first regulation Combustion Fan Regulation Step [RPM] Auger Regulation Step Pag. 68 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
(if is present): so it is possible to create a conversion table [RPM]/[V] to use for the passage from encoder mode P25=1 to not encoder mode P25=0 in case of encoder breakage. Pag. 69 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Default parameters To set the default parameters, use System Evolution Software and set the parameter “ Restore” to 1. Pag. 70 / 70 DMAN802000093-Manual MB250 Hydro Wood-Pellet STD11...
Need help?
Do you have a question about the MB250 and is the answer not in the manual?
Questions and answers