Installation Clearances - Noritz N-084M-DV-CA Owner's Manual And Installation Manual

Table of Contents

Advertisement

Available languages

Available languages

6.

Installation Clearances

Before installing, check for the following:
Install in accordance with relevant building and mechanical codes, as well as any local, state
or national regulations.
Item
• Maintain the following clearances
from both combustible and
non-combustible materials.
• If possible, leave 203mm (8") or more on
either side of the unit to facilitate inspec-
tion.
• If possible, leave 610mm (24") or more in
front of the unit to facilitate maintenance
and service if necessary.
• There must be a clearance of 610mm
(24") or more in front of the Flue termi-
nal.
• This restriction will not be applied to an
area where an effective shield makes a
clearance of 610mm (24") or more in
front of the exhaust outlet.
40
Check
Illustration
305m
(12")
or more
Distance from
the top surface
203mm
(8") or
more
610mm
(24") or
more
There must be no
building opening
within this area.
305mm (12")
or more
Caution
50mm (2")
or more
Distance from
the side
Consult vent
manufacturer
203mm
for clearances
(8") or
more
305mm (12")
or more
Flue terminal
305mm (12")
or more
305mm (12")
or more