 Device installation place must be far way from blockers, obstruction parts and
bulges during repairing and maintenance. There must be sufficient space around
the device for maintenance and repair.
 Electric connection of the device must be made with suitable cable, fuse and
residual current device and grounding absolutely must be made.
 Installation wall of the device must be as durable as carrying the weight of the
device.
5.2. Wall Type Device Installation
Installation wall of the device must be as durable as carrying the weight of the
device.
For device installation in the place chosen in accordance with the conditions stated
above;
 Mark the place of device installation holes on the installed surface
 Drill up and bottom installation holes with 8 mm drilling bit.
 Place M8 open hook steel dowelto to upper installation hole and tighten the nut
until fixing plug tighten. The open side of hook must be up.
 Install the 8 mm fixing plug to bottom part installation holes.
 After control durability of hook, hold the device by two people opposite to each
other, place it on the hanger upper plate fixed to the wall. Do not leave the device
without being sure that it is fully fixed.
 Fix tightly from bottom installation holes with 5*45mm Chipboard Screws.
 After complete the wall installation of device, control the installation durability of
device.
For Ukdax-xxHBT ve Ukdax-xxHBM models, 50 K NTC boiler sensor must be
installed.
18