Eh 03 / Ec 07 (Fan Speed Is Operating Outside Of The Normal Range Diagnosis And Solution) - MrCool DIY E Star Series Troubleshooting Manual

Hide thumbs Also See for DIY E Star Series:
Table of Contents

Advertisement

7.4
EH 03 / EC 07 (Fan speed is operating outside of normal range diagnosis and solution)
Description: When indoor / outdoor fan speed keeps too low or too high for a certain time, the LED displays the failure
code and the AC turns off.
Recommended parts to prepare:
• Connection wires
• Fan assembly
• Fan motor
• PCB
Troubleshooting and repair:
Power off, then restart the unit after 2 minutes.
Shut off the power supply, Rotate
Check the wiring of fan motor.
the fan motor from the PCB.
Is it within normal parameters?
Note: For certain models, outdoor PCB could not be removed separately. In this case, the outdoor electric
control box should be replaced as a whole.
Does a problem remain?
YES
the fan by hand.
Does it turn easily?
YES
Is it improperly wired?
YES
Measure the voltage for
YES
Replace the fan motor
Troubleshooting 22
NO
The unit is operating normally
NO
Find the cause of the problem and resolve it
Ensure proper connections
NO
Replace the PCB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents