MYERS LVM-125 Installation Manual

MYERS LVM-125 Installation Manual

Advertisement

Quick Links

LVM-125/250
( L V S Ca t a l o g #: CE P S - 1 2 5 / 2 5 0 )
INSTALLATION MANUAL
EMERGENCY POWER EQUIPMENT
UNIVERSAL MICRO INVERTER
PURE SINUSOIDAL AC OUTPUT
OUTPUT VOLTAGE AUTO SETTING EQUAL TO INPUT VOLTAGE
AUTO DIMMING (0-10V) OF CONNECTED LOAD
IMPORTANT SAFEGUARDS
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED,
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. To prevent electric shock, switch off the mains power until installation is complete and
AC input power is supplied to this product.
2. This product requires an unswitched AC power supply of 120-277V, 50/60Hz.
3. Ensure all connections are in accordance with National Electrical Code or Canadian
Electrical Code and all local regulations.
4. To reduce the risk of electrical shock, disconnect both normal power, emergency power
supplies and unit connector of this product before servicing.
5. For emergency operation of LED, incandescent, fluorescent fixtures and screw-base
lamps.
6. The product has a metallic housing and is suitable for installation in air handling/plenum
spaces in accordance with the National Electric Code.
7. Use this product in 0°C minimum, 50°C maximum ambient temperatures (Ta). To ensure
the emergency operating time over 90 minutes, the output emergency power of LVM-125
/250 should be maximum of 125W for the LVM-125 and 250W for the LVM-250.
8. Use with grounded, Listed, dry or damp location rated fixtures and the case should be
grounded.
9. Do not use outdoors. Do not mount near gas or electric heaters.
10. The use of accessory equipment not recommended by the manufacturer may cause an
unsafe condition and void warranty.
11. Do not use this product for other than intended use.
12. Installation and service should be performed by qualified service personnel.
13. This product should be mounted in locations and at heights where it will not readily be
subjected to tampering by unauthorized personnel.
THIS PRODUCT CONTAINS A RECHARGEABLE LITHIUM IRON PHOSPHATE BATTERY.
THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.
LFP
WWW.MYERSEPS.COM
WWW.LVSCONTROLS.COM
44 South Commerce Way, Bethlehem, PA 18017
INSTRUCTION MANUAL
INCLUDING THE FOLLOWING
SAVE THESE INSTRUCTIONS
Technical Support: 610-868-5400
10E22
3KLH
E95719

Advertisement

loading
Need help?

Need help?

Do you have a question about the LVM-125 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for MYERS LVM-125

  • Page 1 90 minutes, the output emergency power of LVM-125 /250 should be maximum of 125W for the LVM-125 and 250W for the LVM-250. 8. Use with grounded, Listed, dry or damp location rated fixtures and the case should be grounded.
  • Page 2: Installation

    INSTALLATION CAUTION: MAKE CERTAIN THE AC POWER IS OFF AND THE LVM-125/250 BATTERY SWITCH IS DISCONNECTED UNTIL THE INSTALLATION IS COMPLETE. 1. SPECIFICATION OF LVM-125/250 Voltage Output Power Input Output LVM-125 LVM-250 120V 60Hz 120V 60Hz 230V 50Hz 230V 50Hz...
  • Page 3: Surface Mounting

    Dimension unit: mm [inch] Weight M1 (Hanging) M2 (Mounting) Item No. mm [inch] mm [inch] mm [inch] mm [inch] mm [inch] kg [lb] LVM-125 252 [9.92] 282 [11.10] 292 [11.50] 175 [6.89] 85 [3.35] 4.2 [9.24] LVM-250 358 [14.09] 388 [15.28] 398 [15.67] 175 [6.89]...
  • Page 4 CAUTION: DO NOT TURN BATTERY SWITCH ON UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED. 1. The LVM-125/250 requires an unswitched AC power supply of 120-277 volt, 50/60Hz. 2. Refer to the wiring diagrams below. 3. Consult the factory for other wiring diagrams.
  • Page 5: Operation / Testing / Maintenance

    2. Preprogrammed Scheduled Auto Test a) The LVM-125/250 will conduct the first Monthly Auto Test after 24 hours and up to 7 days after initial power on. Then monthly tests will be performed every 30 days.