Sensor Setting - ETC echoflex OWS-IR-UW-120/277 Installation Manual

Wall switch sensor
Table of Contents

Advertisement

Echoflex Installation Guide
Wall Switch Sensor

Sensor Setting

The Sensor Setting adjusts PIR Sensitivity, Audio Sensitivity, and Sensor
Occupancy Timer duration. To reduce false occupancy states caused by
external elements, consider adjusting the sensitivity setting.
1. Press and hold the [Teach] button until all the LEDs blink once.
Release the button to enter the menu and display the first item, the
blinking red LED.
2. Press and release the [Teach] button to cycle through the menu of
color LEDs and stop when the red and yellow LEDs are both blinking.
3. Press and hold the [Teach] button until the LEDs stop blinking to
select Sensor Setting.
4. Press the [Teach] button to cycle through the options:
Two green blinks - PIR Sensitivity
Two yellow blinks - Audio Sensitivity (DT model only)
Two red blinks - Occupancy Timer (DT model only)
Note:
Echoflex Dual Tech sensors have a configurable Occupancy
Timer that sends a vacancy message when expired. If using another
brand of controller with a DT model, you may want to adjust the
Occupancy Timer on the sensor to control vacancy messaging.
5. Press and hold the [Teach] button again to select an option. The
corresponding LED blinks according to the current setting.
6. Press the [Teach] button to cycle through the settings.
Blinks
1
2
3
4
5
6
7. Press and hold the [Teach] button for 10 seconds to save and exit.
Note:
active the full duration of the Audio Enabled Timer. Disabling both
the Occupancy Timer and Audio Sensitivity sets the sensor to
detect PIR only.
Wall Switch Sensor
PIR Sensitivity
Green LED
High (default)
Medium
Low
If the Occupancy Timer is disabled, the audio remains
Audio Sensitivity
Yellow LED
Automatic (default)
Low
Disabled
Page 9 of 12
Occupancy Timer
Red LED
Disabled
5 mins
10 mins
15 mins
20 mins (default)
25 mins
Echoflex