Reviewing/Revising Data - Intermatic ET70415CR User Manual

Intermatic et70415cr time switches: user guide
Table of Contents

Advertisement

INSTRUCTIONS FOR REVIEWING/REVISING DATA
REVIEW PROCEDURE
• Place the RUN/SET switch in the SET position to review.
• You must review Clock info (day of week, time, date), Astro and
Holiday dates in SET UP mode.
• You must review all load activity (Fixed times, Astro times, Pulse
operations, Interval operations and special "Holiday" load
activities) in PROGRAM mode.
• In PROGRAM, select only one load at a time using the
Enable switch. If more than one circuit is enabled, you will
only see switch activities common to all Enabled circuits.
REVIEW CLOCK, CALENDAR, ASTRO DATA AND
HOLIDAY DATES
To initiate review, press SET UP (day of week/time are displayed),
then press REV (Review). Continue to press REV for each program
you wish to review. SET UP stops after the time is displayed if no
ASTRO information has been entered, allowing you to enter
Astro data (Zone, Sunrise and Sunset). If ASTRO information has
been entered, pressing REV after reviewing the Sunset time will
cause the message "End of Review" to be displayed. Review will
then automatically advance to HOLIDAY, allowing you to select a
specific holiday reference # (01–99) for review. If you want to
review all holiday dates, press REV without selecting a reference
number, and the first holiday reference # will appear. (This will
not necessarily be reference #1 since holidays review in
chronological order beginning January 1st). Continue to press
REV to walk through the Ref # and the Start and Stop dates for
each holiday until "End of Review" is displayed. For single day
holidays, Start and Stop dates will be the same. Note that Astro
sunrise and sunset times are re-calculated daily by the timer and
will differ from times entered or reviewed on a previous date.
REVISE SET UP DATA
To revise or delete displayed information during Set Up Review,
simply press CLEAR. When reviewing Astro Sunrise and Sunset
times, you may need to press CLEAR more than one time since
12
each operation deletes only one digit. You can then immediately
make the revision. Be sure to press OK to enter the new data.
Note that after any revisions to the sunrise Astro time, the sunset
Astro time must be re-entered and okayed. Press REV to continue
the review.
REVIEW PROGRAM
• Be sure to select one load at a time. Failing to do so will allow
you to only review switching activities which are common to all
the circuits selected. In other words, if circuits #1 and circuits #2
are both enabled and are both programmed to come ON at 8:00
A.M., but OFF at different times, the 8:00 A.M. ON time will
be the only set point shown in Review. You must be in the
PROGRAM mode in order to review the programmed load
activities.
• In the PROGRAM mode, you can review switching activities
regardless of whether you programmed them as Fixed Times,
Astro Times, Pulse Switching or Interval Switching. Special
Holiday load activities or interval overrides are also reviewed in
Program.
REVIEW WEEK LONG SWITCHING ACTIVITIES
The normal load switching schedule is a composite of all
applicable individual day schedules, day group schedules and
copied days.The week long review feature allows this composite
schedule to be easily reviewed; by simply pressing the REV key
repeatedly, without first selecting a day, the timer will step thru all
scheduled switching times chronologically, beginning at 12:00
A.M. Sunday, or by pressing the REV key once, then pressing the
OK key, the timer will automatically step thru each scheduled
switching time, displaying each time for about 2 seconds. Press the
OK key to pause auto review. Press the OK key again to resume
auto review; or press the REV key to continue review manually.
The scheduled switching times may only be reviewed, not cleared
during week long review. Follow the steps below for individual
day/day group review if any scheduled events need to be cleared.
Next Generation