Following are guidelines for preventing ESD damage:
Always use an ESD strap and ensure that it makes good skin contact.
When removing or installing an LED board, connect the equipment end of the ground strap to an
unpainted surface of the chassis, such as the vertical metal frame that is exposed when the front
chassis panels are removed.
Handle boards by the edges only; avoid touching the board components, traces, or connector
pins.
Place a removed board component-side-up on an antistatic surface or in a static shielding bag. If
you are returning the board to the factory, immediately place it in a static shielding bag to avoid
ESD damage.
Avoid contact between the board and clothing. The wrist strap only protects the board from ESD
voltages on the body; ESD voltages on clothing can still cause damage.
Caution
should be within the range of 1 and 10 megohms.
Preparing the Work Area
Although some network downtime is unavoidable while you remove the RP and SP and replace them
in the new chassis, you can minimize network downtime by placing the old and new chassis close
together. If your existing chassis is mounted in a rack, and there is space in the same rack or another
rack close by, install the new chassis in the rack before shutting down the existing chassis. Leave
network interface cables connected to the interface ports only if the following conditions are true:
You are able to place the new chassis next to the existing chassis, and moving the processor
modules to the new chassis will not strain the interface cables.
You will not have to lift the new chassis after the processor modules and power supplies are
installed.
The new chassis is already located in its permanent location, or you will need to move it only a
few feet into the space vacated by the old chassis when it is removed.
Before removing an existing chassis that is rack mounted, you are able to install the new chassis
in the same rack or an adjacent rack, and moving the processor modules to the new chassis will
not strain the interface cables.
If these conditions are not true, for instance, if you must remove a rack-mounted chassis before you
can install the new chassis, you must disconnect all power and network interface cables.

Unpacking the Chassis

To unpack the new chassis, follow the directions in the document Cisco 7000 and Cisco 7507
Unpacking Instructions (Document Number 78-1067-xx), which ships with every new chassis; this
document is also available on UniverCD.

Replacing a Rack-Mounted Chassis

This section describes how to replace the chassis in a system that is installed in an equipment rack.
The order in which you remove the existing system, install the new chassis, and replace the
components will vary depending upon the space available in the rack and in the work area. Assess
your rack and lab configuration and choose the appropriate replacement plan from the following:
For safety, periodically check the resistance value of the antistatic strap. The measurement
Cisco 7000 and Cisco 7507 Chassis Replacement Instructions