Precautions - Toshiba TOSVERT VF-AS1 Instruction Manual

Commercial power supply backup and commercial power supply/inverter switching
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

Title
Output signal selection of commercial

power/inverter switching
*3

Inverter side switching waiting time
Commercial power side switching waiting
*3

time
*1

Input terminal selection #6 (S2)

Output terminal selection #1 (OUT1)

Output terminal selection #2 (OUT2)
*1:Be careful about Items 5 and 7 in 1.3, "Precautions."
*2:Due to internal processing timing, inverter-side wait time become 0.5 second longer than the setting value of 
*3: and  are included the operation time of the relay and the magnet contactor.
In almost all cases, it is not necessary to change these parameter settings.

1.3. Precautions

1. Make sure to interlock the magnetic contactor (MC3) on the inverter output side with the
commercial power supply magnetic contactor (MC1).
2. Magnetic contactor (MC2) can be omitted for normal operation but this is needed to isolate the
inverter circuit in case a short-circuit fault occurs inside the inverter. Examine whether it should
be installed or not considering the importance of the system concerned.
3. Check to make sure the phase sequence of the inverter and that of the commercial power
supply are the same beforehand to maintain the motor's rotational direction unchanged before
and after the power switching.
4. In the

(
=2). Switching to commercial power supply cannot be made because the inverter

cannot run forward.
5. If the cause of the inverter trip was OCL (short-circuit on the load side at startup), E (emergency
stop) or EF1, 2 (ground fault), commercial power supply /inverter switching output 1, 2 (output
terminal selection 46, 48) are both shut off and MC1 and MC3 on both inverter and commercial
power supply sides disabled and unable to turn on.
6. In case an inverter trip occurs, remove the cause of the protective action and then reset the
inverter to start the inverter again.
7. S2 terminal (emergency stop) can be omitted, but it is needed as a circuit to detect a motor
overload when the motor is operated on commercial power supply. Examine whether it should
be installed or not considering the importance of the system concerned.
8. Regarding the selection of MCCB used when the backup circuit starts in star delta configuration,
you have to consider the peak current when star connection is switched to delta connection.
9. In the case the motor's connection is star-delta, use delta connection when the inverter is
running. (Do not switch star delta connection while the inverter is running.)
Function
(Reverse-run prohibition), do not use the forward direction disable setting
Adjustment range
0 to 3
0.1 to 10.0 seconds
0.37 to 10.0 seconds
0 to 135
0 to 119
0 to 119
6
E 6 5 8 1 3 6 4
Setting value
1 (Automatic switching when
tripped)
Different for each model
0.62
20
(Emergency stop)
46
(Commercial power/inverter
switching output 1)
48
(Commercial power/inverter
switching output 2)