Mounting Requirements - Endress+Hauser Liquiphant FTL64 Brief Operating Instructions

Hide thumbs Also See for Liquiphant FTL64:
Table of Contents

Advertisement

Liquiphant FTL64
 1
Installation examples for a vessel, tank or pipe
1
Vessel insulation (example with temperature spacer)
If process temperatures are high, the device should be included in a vessel insulation system to prevent
the electronics from heating as a result of thermal radiation or convection.
5.1

Mounting requirements

NOTICE
Scratches or impacts damage the coated surface of the device.
Ensure the device is handled properly and professionally during all mounting work.
5.1.1
Take switch point into consideration
The following are typical switch points, depending on the orientation of the point level switch.
Water +23 °C (+73 °F)
Minimum distance between the fork tip and the tank wall or pipe wall: 10 mm (0.39 in)
Endress+Hauser
1
Mounting
A0042329
7