I Basic Functions Of The Service Valves; I Pump Down - Sanyo CH1872 Technical & Service Manual

Dc inverter split system air conditioner
Hide thumbs Also See for CH1872:
Table of Contents

Advertisement

I
Basic Functions of the Service Valves
The basic functions of the service valves are given in Table 8 below.
Table 8
Action
Shipping
Operating and
test running
the air conditioner
Measuring pressure
and gas charging
Air purging with
a vacuum pump
CAUTION
When opening or clos-
ing the service valve
stem, use the accessory
hex wrench. Be sure to
fully seat the wrench
before turning the valve.
I
Pump Down
Pump down means collecting all refrigerant gas in the
system back into the outdoor unit without losing any of
the gas. Pump down is used when the unit is to be
moved or before servicing the refrigerant circuit.
Pump Down Procedure
Be sure to carry out pump down with the unit in
cooling mode.
(1) Connect the Lo side charging hose of the manifold
valve to the service port on the wide tube service
valve.
Narrow Tube Service
Valve (2-Way)
CLOSED
Fully OPEN
Fully OPEN
CLOSED
Close
Open
Hex
wrench
Fig. 60b
Wide Tube Service
Valve (3-Way)
O-ring
Valve cap
Stem
*
*
Hose with push-pin
PUSH
(2) Using a hex wrench, turn the narrow tube service
valve clockwise all the way to close the service
valve. (Be sure to confirm that the wide tube service
valve is fully open.)
(3) Press the operation button and start cooling oper-
ation.
(4) When the low pressure gauge reading falls to 14.2 to
7.1 psi (1 to 0.5 kg/cm
valve stem. Then quickly stop the unit.
(5) Disconnect all gauges and hoses, and replace the
valve caps as they were before.
22
* The service port on the wide tube ser-
vice valve uses a Schrader core valve
to access the refrigerant system.
Therefore, be sure to use a hose con-
nector which has a push-pin inside.
(Fig. 60a)
Service valve
NOTE
External diameter of service port
R410A: 5/16"
Fig. 60a
2
), fully close the wide tube

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents