Powerware 5119 User Manual page 24

1000-3000 va
Table of Contents

Advertisement

Configuration
LED
Option
Shutdown Delay
AC Input Failure
Sleep Mode
100/208V Nominal
Input Voltage
100/208V Extended
Voltage Mode
Reset Defaults
18
Power On
Explanation
Indicator
ON (default)
5-second delay before unconditional shutdown after the UPS receives a signal
from a computer via the communication port.
OFF
180-second delay before unconditional shutdown after the UPS receives a signal
from a computer via the communication port. When this LED is not enabled, the
user can also create a new delay time by reconfiguring the communication port.
See "Communication Port Configurations" on page 25 for more information.
ON (default)
Alarm sounds when there is an AC input failure.
OFF
Alarm DOES NOT sound when there is an AC input failure.
ON (default)
When the UPS is on battery and the load is drawing less than 5% of the current,
the UPS shuts down the load. This feature conserves battery power.
OFF
Select this option if you want a load less than 5% of the current to be protected
by battery power.
ON*
Selecting this option changes the nominal input voltage on low voltage models
to 100V and to 208V on high voltage models.
*This is the default for factory-configured 100V or 208V models (see the rating
label on the UPS rear panel).
OFF (default)
100/208V is disabled; one of the other input voltage options is selected.
ON
Select this option to extend the input voltage within -25% to +25% of 100V or
208V nominal input voltage before switching to battery (available on units that
were specifically ordered with this option).
OFF (default)
The UPS accepts an input voltage within -20% to +20% of 100V or 208V
nominal input voltage before switching to battery.
ON (default)
All factory-set defaults are active.
OFF
One or more factory-set defaults have been changed.
Powerware
5119 User's Guide
®
: