TECO JNTHBCBA0001BEAU Manual

TECO JNTHBCBA0001BEAU Manual

For constant-pressure pump
Table of Contents

Advertisement

Advertisement

Chapters

Table of Contents
loading
Need help?

Need help?

Do you have a question about the JNTHBCBA0001BEAU and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TECO JNTHBCBA0001BEAU

  • Page 2: Table Of Contents

    Table of Content Preface ......................... 1 Chapter 1 Definition of Model..................2 Chapter 2 Safety Precautions..................3 2.1 Operation Precaution................... 3 2.1.1 Before Power ON ..................3 2.1.2 During Power ON ..................4 2.1.3 Before Operation ..................4 2.1.4 During Operation ..................4 2.1.5 During Maintenance...................
  • Page 3: Preface

    ※Products Inspection TECO’s inverters are all passed the function test before delivery. Please check the followings when you received and unpacked the inverter: The model and capacity of the inverter are the same as those specified in your purchase order.
  • Page 4: Chapter 1 Definition Of Model

    : 4.2A OUTPUT : AC 3 phases 0~400Hz → Output specifications VOLTAGE : 0~480V Amps : 2.3A TECO Electric & Machinery Co., Ltd. JNTH 0001 Series: UL Approval : Keypad Panel U : YES Horsepower : BC : LED R500 : 0.5 HP...
  • Page 5: Chapter 2 Safety Precautions

    Chapter 2 Safety Precautions 2.1 Operation Precaution 2.1.1 Before Power ON Caution The line voltage applied must comply with the inverter’s specified input voltage. Danger Make sure the main circuit connections are correct. L1(L), L2 and L3(N) are power-input terminals and must not be mistaken for T1, T2 and T3. Otherwise, the inverter might be damaged.
  • Page 6: During Power On

    2.1.2 During Power ON Danger Do not plug or unplug the connectors on the inverter when electrified to avoid the control panel damage resulting from erratic transition voltage surge due to contact bounce. 2.1.3 Before Operation Caution The inverter will flash the power voltage 5 seconds when applying power. During Operation 2.1.4 Danger...
  • Page 7: During Maintenance

    2.1.5 During Maintenance Caution The inverter should be used in a non-condensed environment with temperature from –10 degree C to +40 degree C and relative humidity of 95% non-condense. Caution When the inverter top cover has removed, it can be used in a non-condensed environment with temperature from –10 degree C to +50 degree C and relative humidity of 95%, but the environment should be free from water and metal dust.
  • Page 8: Chapter 3 Notice For Wiring

    Chapter 3 Notice for wiring 3.1 Precautions for Peripheral Applications Power supply: Make sure the voltage applied is correct to Power avoid damaging the inverter. A molded-case circuit breaker must be installed between the AC source and the inverter Molded-case circuit breaker: Use a molded-case circuit breaker that Molded-case conforms to the rated voltage and current of...
  • Page 9: Fuse Types

    (Short circuit protection only), suitable for protection of Power semiconductors. TECO Molded case circuit breakers can be used in Place of the input fuse, consider the necessity of back up fuse to provide correct protection according to the applicable national and international regulations.
  • Page 10 ※Notice To avoid shock hazards, do not touch any electrical component when the power is applied or just after five minutes the power plug is unplugged. The other action should be performed after the charge indicator went off. Do not perform wiring on the inverter while it is still electrified. Disregard of this notice could cause serious injure or death to persons.
  • Page 11: Inflammable Materials

    3.3 Inflammable materials A. Screwdriver torque: Wiring with a screwdriver or other tools and follow the torque listed below: Securing torque Horsepower Power source Nominal torque for TM1 terminal 0.5/1/2(3φ) 200-240V 0.59/0.08 7.10/8.20 (LBS-FT / KG-M) (LBS-IN/KG-CM) 1/ 2 380-480V 2(1φ)/3/5/7.5/10 200-240V 1.5/0.21...
  • Page 12: Specifications

    3.4 Specifications Single phase, 200-240V model JNTHBCBA□□□□ACAU(F) R500 0001 0002 0003 Horsepower(HP) Suitable Motor Capacity(KW) 0.75 Rated Output Current(A) 10.5 Rated Capacity(KVA) ± 5% Max. Input Voltage Single Phase: 200~240V +10% -15%,50/60H Max. Output Voltage Three Phases: 0~240V Input Current(A) 23.9 Net Weight(KG) 1.2(1.3)
  • Page 13: Wiring Diagram Cvp Series Inverter

    3.5 Wiring Diagram CVP Series Inverter Wiring diagram I: Braking reactor Resistor(note1) Molded-case circuit breaker Install fast Magnetic Induction action fuse MCCB contactor motor L1(R) T1(U) Power Power T2(V) Power L2(S) input output source T3(W) L3(T) 200V: Class 3 ground ON-OFF 400V: Special ground Burst absorber...
  • Page 14 Wiring diagram II: Note 1: Please refer to description of main circuit terminals (P1, BR) and specification of braking resistor for value selection. Note 2: Above wiring diagram refers for 2.2~30KW at 220V and 2.2~55KW at 440V.
  • Page 15: Pump Wiring Diagram Of Control Board

    3.6 Pump Wiring Diagram of Control Board 1. Single pump wiring diagram. (I) Pressure Single pump parameter Transmitter setting:19-0=0 Switch 20-0 = 1 (External Control) Single pump wiring diagram 2. Dual pump wiring diagram. (I) Pressure Transmitter Dual pump parameter setting : Switch 19-0 = 1(Dual pump : Master)
  • Page 16 3. Single pump wiring diagram. (II) 20-0 = 1 (External Control) Single pump parameter setting : 19-0=0 Switch AGND Pressure Transmitter Single pump wiring diagram 4. Dual pump wiring diagram. (II)
  • Page 17: Description Of Terminals Troubleshooting Inverter

    3.7 Description of Terminals Troubleshooting Inverter Descriptions of main circuit terminals Symbol Description R / L1 ( L ) Main power input Single-phase: L/N S / L2 Three-phase: L1/L2/L3 T / L3 ( N ) Braking resistor or connecting terminal: Used in cases where the inverter frequently disconnects due to large load inertia or short 220V:0.5~10HP, deceleration time (refer to specifications of braking resistor)
  • Page 18: Outline Dimension

    Descriptions of SW function Type of Type of SW2/SW3 Remarks external Remarks external signal signal 0~10VDC NPN (SINK) analog signal input Factory setting is voltage input 0~20mA Factory (SOURCE) analog signal default input 3.8 Outline Dimensions (1) Frame1: Single phase JNTHBCBA __ AC: R500, 0001 Three phase JNTHBCBA __ BC/BE: R500, 0001, 0002 (2) Frame2: Single phase JNTHBCBA __ AC: 0002, 0003 Three phase JNTHBCBA __ BC/BE: 0003, 0005...
  • Page 19 (3) Frame3: (4) Frame4: Three phase JNTHBCBA __ BC: 7R50, 0010 Three phase JNTHBCBB __ BC: 0015, 0020, 0025 JNTHBCBA __ BE: 7R50, 0010, 0015 JNTHBCBB __ BE: 0020, 0025, 0030 4-Ø5.5 4-Ø7.0 (5) Frame5: Three phase JNTHBCBA __ BC: 0030, 0040 JNTHBCBA __ BE: 0040, 0050 (6) Frame6: Unit:...
  • Page 20: Chapter 4 Software Index

    Chapter 4 Software Index 4.1 Operation Instruction of the Keypad ● :LED Light Lit :LED Light Flash Power Voltage 5 second later or Press DSP to modify pressure value Pressure (Bar) *1 Target Pressure Value (Setting) < Target Feedback HZ/RPM (stop) (flash) HZ/RPM RUN/STOP...
  • Page 21: Programmable Functions List

    4.2 Programmable Functions List Parameter Description Group No. Drive Status and Function Reset Operation Parameters PID Control Parameters System Protect Parameters Dual Pumps Parameters Multifunction Input/ Output Parameter Group...
  • Page 22 15-Group Drive Status and Function Reset Function Factory Communication Description Range (unit) /Code Remarks Code No. Setting Address Drive Horsepower 15-0 134 or (0x86) Code 15-1 Software Version 135 or(0x87) Fault Jog 15-2 136 or(0x88) (Last 3 Faults) Accumulated 15-3 0 - 9999 139 or(0x8B) Operation Time(Hours)
  • Page 23 17-Group PID Control parameters Function Communication Description Range (unit) /Code Factory Setting Remarks Code No. Address 17-0 Proportional Gain (P) 0.0 – 10.0 111 or (0x6F) 17-1 Integration Time (I) 0.0–100.0 (sec) 1.0 (sec) 112 or (0x70) 17-2 Differentiation Time (D) 0.00 – 10.00 (sec) 0.00 (sec) 113 or (0x71) 17-3...
  • Page 24 19-Group Dual Pumps Parameters Communication Function Description Range (unit) /Code Factory Setting Remarks Address Code No. 0 : Single 1 : Dual – Master Single/Dual Pump 19-0 2 : Dual – Slave 1 172 or (0xAC) Master/Slave Selection 3 : Dual – Slave 2 4 : Dual –...
  • Page 25 20-Group 多 機 能 輸 入 輸 出 參 數 群 Function Communication Description Range (unit) /Code Factory Setting Remarks Address Code No. 0 : Keypad 20-0 Run command source 9 or (0x09) 1 : External Terminal 0 : Forward 20-1 Terminal S1 Function 53 or (0x35)
  • Page 26 Function Communication Description Range (unit) /Code Factory Setting Remarks Address Code No. Gain control of 20-B multifunction analog 0 - 200 78 or (0x4E) output 0 :Reverse available Reverse Function 20-C 11 or (0x0B) 1 :Reverse unavailable Notes: *1 Modify parameter when inverter status is “STOP”, can not change while inverter status is “Run”.
  • Page 27 (1):15-0 Drive Horsepower Code 15-0 Inverter Model 15-0 Inverter Model R500AC / BC 0001BE 0001AC / BC 0002BE 0002AC / BC 0003BE 0003AC / BC 0005BE 0005BC 7R50BE 7R50BC 0010BE JNTHBCBA 0010BC 0015BE JNTHBCBA 0015BC 0020BE 0020BC 0025BE 0025BC 0030BE 0030BC 0040BE 0040BC...
  • Page 28 (5): 15-6 Reset the factory setting 1110: Reset the 50Hz factory setting 1111: Reset the 60Hz factory setting (6):15-7 Parameter locking password 0000~0999 Establish the password procedure: 15-7 = 888 (establish the password command) →15-7 = establish the password (establish the password that the customer appoints) → Completion Unlock the parameter: When the parameter is locked, only 15-7 can be used, if want to unlock the parameter, input the primitive password of establishing on 15-7, other parameters can make an...
  • Page 29 (8):15-9 Display of Pressure Setting 0000: Setting and Feedback 0001: Only Setting 0002: Only Feedback 1.) 15-9=0000: Display setting and feedback pressure value on keypad. The 1 and 2 segment is setting pressure value, and 3 and 4 segment is feedback pressure value. 2.) 15-9=0001: Only display setting pressure value.
  • Page 30 (10):16-2 Acceleration time 0.1 – 3600.0 sec 16-3 Deceleration time 0.1 – 3600.0 sec 16-4 Sleep deceleration time 0.1 – 3600.0 sec 10.0 Bar 16-3 18-0 Target Pressure Value Deceleration 16-2 Accelerat S6 or AI2 16-4 Pressure Sleep Feedback PID Sleep Start Decel Output Frequency 16-2...
  • Page 31 (11):16-5 Sleep Frequency 0.00 – 400.00 Hz 16-6 Period of Water Used Detection 0.0 – 200.0 sec 16-7 Acceleration Time of Water Used Detection 0.1 – 3600.0 sec 16-8 Pressure Range of Water Used Detection 0.00 – 2.50 Bar 16-A Direction of water usage 0 : Upward 1 : Downward 16-B Deceleration time of water usage detection 0.1 –...
  • Page 32 16-A=1 Direction of Water Used(Downward) 16-8 Pressure Range of Water Used Detection 18-0 Target Pressure Value Pressure Feedback 16-B time Acceleration Time of Water Used Detection 18-7 Sleep Delay Time 16-5 Sleep Fequency 16-6 Output Period of Water Frequency Used Detection time Continue using Not use...
  • Page 33 Advantage Disadvantage 1. Keep the actual pressure always higher 1. If the lift is too high which cause the than command pressure in the operating operating frequency higher than usual process, especially for strict and precise even if little water usage or not using Direction of applications.
  • Page 34 (13):17-0 Proportional Gain (P) 0.0 – 10.0 rate 17-1 Integration Time (I) 0.0 – 100.0 sec 17-2 Differentiation Time (D) 0.00 – 10.00 sec Overshooting 18-0 Target Pressure Value Stabilize deviation AI2/S6 Feedback signal Stabilize time PID Parameter Adjustment Guide: Increase Setting Decrease Setting Main...
  • Page 35 (14):17-3 Output Filter Time (O) 0.0 – 2.5 sec After adjust filter Before adjust filter Smooth the PWM output by increase filter time setting. Setting a bigger filter time will get a slower system response time. (15):17-4 Feedback Signal (F) Offset 0.00 – 10.00 rate 17-5 Signal Type 0000 : 0 ~10V 0001 : 4 ~ 20mA 17-6 Feedback Signal Scan Time 1 –...
  • Page 36 (16) 17-7 Liquid Leakage Detection Time 0.0 – 10.0 sec 17-8 Change Level within Detection Time 0.01 - 2.50 Bar 17-9 Restart Level for Liquid Leakage Detection 0.01 - 2.50 Bar 17-7 = 0.0(sec) : Disable Liquid Leakage Detection. When pump is sleeping, the pressure value maybe decrease due to the liquid leakage, if the change of pressure value is higher than 17-8, the pump will start again.
  • Page 37 17-7 = 0.0(sec) : Disable Liquid Leakage Detection. When pump is sleeping, the pressure value maybe decrease because liquid leakage, if the change of pressure value is lower than 17-8 during every 17-7 detection time, the pump will keep in sleep mode, until the pressure value is higher than the setting of 17-9 (restart level).
  • Page 38 (17):18-0 0.10 – 25.50Bar Target Pressure Value 18-1 0.10 – 25.50 Bar Max. Pressure limit 18-2 0.10 – 25.50 Bar Min. Pressure limit 18-1 Max. Pressure limit 18-0 Target Pressure Value AI2/S6 Feedback signal 18-2 Min. Pressure limit Time When using PID control, system pressure will intervene (18-1 Max. Pressure limit) and (18-2 Min.
  • Page 39 (19):18-5 Low pressure alarm time 0.0 – 600.0 sec 18-6 Time ow pressure stop time 0.0 – 600.0 sec 18-1 Max. Pressure limit 18-0 Target Pressure Value AI2/S6 Feedback signal 18-2 Min. Pressure limit time Low pressure deceleration time depend by the (16-3 deceleration time) setting.
  • Page 40 Notes: Sleep function can save energy when pressure reached target pressure value. (21):18-9 HiP/LoP/1BrE Protection Auto Restart Times 0 – 999 1.) 18-9=0: Amount of auto restart is infinite. 2.) 18-9=1~999: When amount of auto restart is over 18-9 setting, then inverter never restart, until re-power-on or using reset function.
  • Page 41 18-8 Sleep Tolerance Range 18-0 19-4 Target Pressure Value Launch Delay Time Pressure Feedback time Output Frequency time Output Frequency time A : When dual pump operate, Master start and Slave(1~3) is standing by, then system is operating in the constant pressure. B : When water usage become larger, then the output frequency of Master will increase.
  • Page 42 D : When the water usage become less, through Water Usage Detection, and the output frequency will decrease again, when the water usage reduce to only 1 drive can afford (means still can keep constant pressure), then the output frequency of Slave will decrease again and get into sleeping mode.(More detail about Slave sleeping conditions please refer 19-6 and 19-7).
  • Page 43 When the output frequency of Master is over than 19-7(%) × 16-0, and 19-4 is finished, or output frequency of Slave is less then 16-5 Sleep Frequency, and persist time is bigger than 18-7 Sleep delay time, then Slave will get into sleep mode.
  • Page 44 F. 20-01~05 = 5 Communication control signal switch reserve. G. 20-01~05 = 6 PID function disable When on, the PID function is disable, drive doesn’t concern about the sensor feedback, in the same time, output frequency= 0. H. 20-01~05 = 7 Forced operating frequency This function is match with PID disable function to start the forced operating frequency.
  • Page 45 Target pressure still limit by 18-1(Max. pressure limit), 18-2(Min. pressure limit). Control of multifunction analog output (32):20-A Multifunction analog output selection: 0: Output Frequency 1: Frequency command 2: Output voltage 3: DC voltage 4: Output circuit 5: PID feedback signal 20-B Gain control of multifunction analog output = 0~200% Multifunction analog output terminal (TM2) is a 0~10Vdc analog output, it is selectable as 20-A, and when external voltage meter or peripheral equipment has...
  • Page 46: Chapter 5 Troubleshooting And Maintenance

    Chapter 5 Troubleshooting and Maintenance 5.1 Error display and remedy 5.1.1 Errors which can not be recovered manually Display Error Cause Remedy Connect a parallel RC burst absorber across the magnetizing Program External noise interference problem coil of the magnetic contactor that causes interference EEPROM Faulty EEPROM...
  • Page 47: Error Which Can Be Recovered Manually And Automatically

    Inverter capacity too small Over speed deceleration time (16-2/16-3) OVSP during operating 2. The Current detect circuit 2.Send back to Teco fault Pressure lower than min. 1. Decrease setting value of Low Pressure pressure limit, low pressure min. pressure limit...
  • Page 48: Error Which Can Be Recovered Manually But Not Auto Matically

    Display Error Cause Remedy When feedback pressure is lower than 18-A (Pressure 1. Decrease the value of min. Pressure Loss losing ratio) and longer then pressure limit Stop pressure losing detection 2. Check pressure meter time. 5.1.3 Errors which can be recovered manually but not automatically Display Error Cause...
  • Page 49: General Troubleshooting

    5.2 General troubleshooting Status Checking point Remedy ‧Is the power applied? ‧Turn the power OFF and then ON Is power applied to L1(L), L2, and L3(N) again. terminals (is the charging indicator lit)? ‧Make sure the power voltage is correct. ‧Make sure screws are secured firmly.
  • Page 50: Appendix

    Appendix The definition of Pressure: Where: p is the pressure, F is the normal force, A is the area. Non-SI measures such as pound per square inch (psi) and bar are used in parts of the world Conversion between and P.S.I are list as below formula: / Cm = 14.22 P.S.I 1P.S.I = 0.07...
  • Page 52 目錄 前言 ..........................51 第一章 型號說明......................52 第二章 安全注意事項 ....................53 2.1 使用時之注意事項 ..................... 53 2.1.1 送電前..................... 53 2.1.2 送電中..................... 54 2.1.3 運轉前 ..................... 54 2.1.4 運轉中 ..................... 54 2.1.5 檢查保養時 ....................55 第三章 安裝及注意事項 ..................... 56 3.1 週邊設備之應用及注意事項 ................56 3.2 保險絲的型式...
  • Page 53 前言 0.1 前言 為 了 充 分 地 發 揮 本 變 頻 器 的 功 能 及 確 保 使 用 者 的 安 全 , 請 詳 閱 本 操 作 手 冊 。 當 您 使 用 中 發 現 任 何 疑 難 而 本 操 作 手 冊 無 法 提 供 您 解 答 時 , 請 連 絡 東 元 各...
  • Page 54: 第一章 型號說明

    VOLTAGE : 380~480V (+10%, -15%) Amps : 4.2A OUTPUT : AC 3 phases 0~400Hz 輸出規格→ VOLTAGE : 0~480V Amps : 2.3A TECO Electric & Machinery Co., Ltd. JNTH 0001 系列別 UL 申請 按鍵面板 U:申請 馬力數 BC:LED R500:0.5 馬力 雜訊濾波器 BG:LCD 0001:1.0 馬力...
  • Page 55: 第二章 安全注意事項

    第二章 安全注意事項 2.1 使用時之注意事項 2.1.1 送電前 注意 所選用之電源電壓必須與變頻器之輸入電壓規格相同。 危險 主迴路端子配線必須正確,L1(L)、L2、L3(N)為電源輸入端子,T1、T2、T3 為變頻器 輸出端子,請勿接電源於輸出端子上,以避免造成變頻器的損壞。 注意 搬運變頻器時,請勿直接提取前蓋,應由變頻器本體搬運,以防止前蓋脫落,避 免變頻器掉落造成人員受傷或變頻器損壞。 請將變頻器安裝於金屬類等不燃物材料之上,請勿安裝於易燃性材料上或附近, 以防止發生火災。 若多台變頻器同放在一個控制盤內,請外加散熱風扇,使盤內溫度低於 40℃ 以 下,以防過熱或火災等發生。 請於關閉電源後,再拆卸或裝入操作器,並請按圖操作固定操作器,以免接觸不 良造成操作器故障或不顯示。 警告 本產品係通過 IEC 61800-3 限制區域使用等級. 在某些環境下使用本產品時 , 可能造成 電磁干擾,故在使用前請先進行適當的量測。 注意 為確保周邊設備安全,建議在變頻器輸入側外加高速保險絲,尤其是大馬力系統。所 採用的高速保險絲規格請參閱 P57 。...
  • Page 56: 送電中

    2.1.2 送 電 中 危險 送電中絕不可插拔變頻器上之連接器(CONNECTOR),以避免控制板因插拔所產生之 突波衝入造成損壞。 2.1.3 運 轉 前 注意 電源投入時,變頻器會先閃爍電源電壓 5 秒。 2.1.4 運 轉 中 危險 運轉中不可將馬達機組投入或切離,否則會造成變頻器過電流跳機甚或將變頻器主迴 路燒燬。 危險 變頻器送電中請勿取下前蓋,以防人員感電受傷。 有設定自動再啟動之功能時,馬達於運轉停止後會自動再啟動,請勿靠近機器以 免危險。 停止開關的功能須設定才有效,與緊急停止開關的用法不同,請注意使用。 注意 散熱座、煞車電阻等發熱元件請勿觸摸。 變頻器可以很容易的使馬達由低速到高速運轉,請確認馬達與機械的容許範圍。 使用煞車模組等搭配產品時,請注意其使用之相關設定。 變頻器運轉時,請勿檢查電路板上的信號。 注意 請先確認電源切斷後,在按鍵面板顯示熄滅 5 分鐘後,方可進行拆裝或實施檢查。...
  • Page 57: 檢查保養時

    2.1.5 檢查保養時 注意 變頻器周圍溫度應在 -10℃ ~+40℃ 95%RH 不結露環境中使用 注意 去掉變頻器防塵蓋後 , 則周圍溫度應在 -10℃~+50℃ 95%RH 不結露環境中 使用,但需確保周圍環境無滴水及金屬粉塵。...
  • Page 58: 第三章 安裝及注意事項

    第三章 安裝及注意事項 3.1 週邊設備之應用及注意事項: 電 源 : 電源 請注意電壓等級是否正確,以避免損壞變頻器。 交流電源與變頻器之間必須安裝無熔絲斷路器。 無 熔 絲 斷 路 器 : 無熔線斷路器 請使用符合變頻器額定電壓及電流等級之無熔絲斷路器做變頻器 之電源 ON/OFF 控制,並做變頻器之保護。 無熔線斷路器請勿做為變頻器之運轉/停止切換功能使用。 漏 電 斷 路 器 : 電磁接觸器 請加裝漏電斷路器,防止漏電造成之誤動作,並保護使用人員之 安全。 若加裝漏電斷路器以做漏電故障保護時,請選用感度電流 200mA 以上,動作時間 0.1 秒以上,以防止高頻誤動作。 功率改善 AC 電抗器 電...
  • Page 59: 保險絲的型式

    3.2 保險絲的型式: 當變頻器元件故障時 , 驅動器輸入端裝置保險絲可用來有效地中斷與系統間的連接!而 變頻器的電子式保護線路可用來清除輸出短路及接地故障,而不會讓輸入端保險絲燒 毀!以下是建議裝置保險絲規格表,為了能夠最有效的保護變頻器,應該使用電子式高 速保險絲。 100% 連續 Max.RK5 Max.CC or T JNTHBCBA- 保險絲額定(A) 保險絲額定(A) 輸出電流(A) R500AC 0001AC 0.75 220V 級(單相) 0002AC 0003AC 10.5 R500BC 0001BC 0.75 0002BC 0003BC 10.5 0005BC 17.5 7R50BC 220V 級(三相) 0010BC 13.3 0015BC 11.0 20.6 0020BC...
  • Page 60: 配線規則

    3.3 配線規則 A. 螺絲扭力: 請依照下列表中之螺絲扭力,以螺絲起子或其他工具進行配線工作: 鎖固扭力 馬力數 電源規格 TM1 端子之額定扭力 200-240V 0.59/0.08 7.10/8.20 0.5/1/2(3φ) (LBS-FT / KG-M) (LBS-IN/KG-CM) 380-480V 200-240V 1.5/0.21 18.00/20.28 2(1φ)/3/5/7.5/10 (LBS-FT/KG-M) (LBS-IN/KG-CM) 3/5/7.5/10/15 380-480V 15/20/25 200-240V 1.84/0.3 22.1/30 20/25/30 380-480V (LBS-FT / KG-M) (LBS-IN/KG-CM) 30/40 200-240V 4.42/0.66 53.1/66 (LBS-FT/KG-M) (LBS-IN/KG-CM)
  • Page 61 3.4 規 格 單相,200~240V 機種 JNTHBCBA ACAU(F) R500 0001 0002 0003 □ □ □ □ 馬 力 數 (HP) 適 用 馬 達 容 量 (KW) 0.75 額 定 輸 出 電 流 (A) 10.5 額 定 容 量 (KVA) ±...
  • Page 62: Cvp 配線圖

    3.5 CVP 配 線 圖 配 線 圖 一 ( 1) MCCB (MC) T1(U) L1(R) T2(V) L2(S) T3(W) L3(T) ON-OFF 200V: 400V: CON 2 RS485 RS232 JNSDOP CON1 S6/AI2 250VAC/1A (30VDC/1A) SW2: AIN 0~10V/0~20mA SW3: S6/AI2 0~10V/0~20mA 0~10VDC 2~10V/4~20mA (Ver2.3 I POSITION: 0~20mA V POSITION: 0~10V SW1: NPN/PNP...
  • Page 63 配 線 圖 二 ( 1) MCCB (MC) T1(U) L1(R) T2(V) L2(S) T3(W) L3(T) ON-OFF 200V: 400V: CON 2 RS485 RS232 JNSDOP CON1 250VAC/1A (30VDC/1A) AGND SW2: AIN 0~10V/0~20mA SW3: AI2 0~10V/0~20mA AGND 0~10VDC 2~10V/4~20mA (Ver2.3 I POSITION: 0~20mA V POSITION: 0~10V SW1: NPN/PNP ※註...
  • Page 64: 泵浦控制端子接線圖

    泵浦控制端子接線圖(樣式一) 19-0 20-0 = 1 (...
  • Page 65 (樣式二) 20-0 = 1 ( 19-0 AGND 19-0 = 1( R2B R2A RS485 20-0 = 1 R1B R1C R1A AGND 20-1 = 0 BLACK R2B R2A RS485 19-0 = 2~4( R1B R1C R1A AGND BLACK...
  • Page 66: 變頻器端子說明

    3.7 變 頻 器 端 子 說 明 主迴路端子說明 端子符號 功能說明 R / L1 ( L ) 主電源輸入 單相機種:L / N S / L2 三相機種:L1 / L2 / L3 T / L3 ( N ) 煞車電阻或連接端子 當負載慣量大或減速時間短,而使變頻器 容易過電壓跳脫時使用( 參照煞車電阻規格 ) 220V:0.5~10HP, 440V:1~15HP P1/ P...
  • Page 67: 外型尺寸圖

    SW 的 功 能 說 明 SW2/SW3 外部信號種類 備註 外部信號種類 備註 0~10VDC NPN(SINK) 類比信號 輸入 (1) 出廠設定為 電壓輸入 0~20mA PNP(SOURCE) 出廠設定 類比信號 輸入 3.8 外型尺寸圖 (1) Frame1:單相 JNTHBCBA __ AC: R500, 0001 三相 JNTHBCBA __ BC/BE: R500, 0001, 0002 (2) Frame2:單相 JNTHBCBA __ AC: 0002, 0003 三相...
  • Page 68 (3) Frame3: (4) Frame4: 三相 JNTHBCBA __ BC: 7R50, 0010 三相 JNTHBCBB __ BC: 0015, 0020, 0025 JNTHBCBA __ BE: 7R50, 0010, 0015 JNTHBCBB __ BE: 0020, 0025, 0030 4-Ø5.5 4-Ø7.0 (5) Frame5: 三相 JNTHBCBA __ BC: 0030, 0040 JNTHBCBA __ BE: 0040, 0050 (6) Frame6:...
  • Page 69: 第四章 軟體索引

    第 四 章 軟 體 索 引 4.1 鍵 盤 按 鍵 操 作 說 明 Power On ● : 液 晶 顯 示 燈 (LED)亮 : 液 晶 顯 示 燈 (LED)閃 電源電壓 5 秒後或按 DSP 鍵後,改顯示壓力值 壓力值(Bar) *1 HZ/RPM 設定值...
  • Page 70: 參數一覽表

    4.2 參數一覽表 參 數 群 組 說 明 變 頻 器 狀 態 與 功 能 復 歸 馬 達 運 轉 參 數 群 PID 控 制 參 數 群 系 統 保 護 參 數 群 雙 泵 浦 參 數 群 多...
  • Page 71 15-Group 變 頻 器 狀 態 與 功 能 復 歸 功能 功能 範 圍 / 代 碼 出廠設定 通訊位址 備 註 代碼 15-0 變頻器馬力代碼 134 or (0x86) 軟體版本 15-1 135 or(0x87) 15-2 故障記錄 136 or(0x88) 累積工作時間 1 15-3 0 - 9999 139 or(0x8B) (1 Hours) 累積工作時間...
  • Page 72 功能 功能 範 圍 / 代 碼 出廠設定 通訊位址 備 註 代碼 0 : 用水檢測向上 16-A 用水檢測方向 244 or (0xF4) *1 *5 1 : 用水檢測向下 用水檢測減速時間 16-B 0.1 – 3600.0 (sec) 40.0 (sec) 245 or (0xF5) 17-Group PID 控 制 參 數 群 功能...
  • Page 73 功能 功能 範 圍 / 代 碼 出廠設定 通訊位址 備 註 代碼 18-A 失壓比例 0 - 100 (rate) 0 (rate) 229 or (0xE5) 18-B 失壓檢測時間 0.0 – 25.0 (sec) 0.0 (sec) 239 or (0xEF) 強制設定頻率運 18-C 0.0 – 200.0 (Hz) 0.0 (Hz) 240 or (0xF0) 轉...
  • Page 74 20-Group 多 機 能 輸 入 輸 出 參 數 群 功能 功能 範 圍 / 代 碼 出廠設定 通訊位址 備 註 代碼 0 : 按鍵面板 20-0 運轉命令來源選擇 9 or (0x09) 1 : 外部端子 0 : 正轉指令 端子 S1 功能設定 20-1 53 or (0x35) 1 : 外部急停...
  • Page 75 註 *1 變頻器運轉中無法修改 *2 需要搭配 SW3 選擇 *3 軟體版本 Vb1.2 版後新增與修改參數 *4 軟體版本 Vb1.4 版後新增與修改參數 *5 軟體版本 Vb1.5 版後新增與修改參數 *6 軟體版本 Vb1.6 版後新增與修改參數 18-0 (0.10~10.00 Bar) 17-0 Filter 17-3 17-1 17-2 (S6) (AI2) Filter Signal Gain 17-5 17-6 17-4 0 : 0~10v 1 : 4~20mA Output Motor...
  • Page 76 (1): 15-0 變 頻 器 馬 力 代 碼 15-0 變頻器型號 15-0 變頻器型號 R500AC / BC 0001BE 0001AC / BC 0002BE 0002AC / BC 0003BE 0003AC / BC 0005BE 0005BC 7R50BE 7R50BC 0010BE JNTHBCBA 0010BC 0015BE JNTHBCBA 0015BC 0020BE 0020BC 0025BE 0025BC 0030BE...
  • Page 77 (5):15-6 出廠設定功能 1110: 將參數復歸(RESET) 為出廠值(50Hz) 1111: 將參數復歸(RESET) 為出廠值(60Hz) (6):15-7 參數鎖定密碼 0000 ~ 0999 設定密碼程序: 15-7 = 888(設定密碼命令) → 15-7 = 設定密碼(設定客戶指定之密碼) → 完成 解除參數鎖定: 參數鎖定時,僅 15-7 參數可設定,若欲解除參數鎖定,請於 15-7 輸入原設定密碼後, 即可解除,解除後其餘參數方可做修改與設定。 強制密碼清除: 若忘記原設定之密碼時,可以此程序先清除原先密碼之設定,後續若有需要做密碼鎖定 時,請重覆上述『設定密碼程序』操作 15-7 = 123(清除密碼命令 1) → 15-7 = 999(清除密碼命令 2) → 原密碼已清除 註:1.變頻器若要設定密碼時,請先輸入原設定密碼,解除參數鎖定後,才可使用設定密...
  • Page 78 (9):16-0 運轉頻率上限 0.01 – 400.00 Hz 16-1 運轉頻率下限 0.00 – 400.00 Hz 400.00Hz PID Output 16-0 運轉頻率上限 Motor Output 16-1 運轉頻率上限 0.01 Hz 限制馬達運轉在額定範圍。 下限可增加打水時的反應速度與減少回水震動。 上限可避免回授訊號故障導致馬達過轉速運行。 (10):16-2 運轉加速時間 0.1 – 3600.0 sec 16-3 運轉減速時間 0.1 – 3600.0 sec 16-4 休眠減速時間 0.1 – 3600.0 sec 10.0 Bar 18-0 16-3...
  • Page 79 (11):16-5 休眠頻率 0.00 – 400.00 Hz 16-6 用水檢測週期 0.0 – 200.0 sec 16-7 用水檢測加速時間 0.1 – 3600.0 sec 16-8 用水檢測壓力範圍 0.00 – 2.50 Bar 16-A 用水檢測方向 0 : 用水檢測向上 1 : 用水檢測向下 16-B 用水檢測減速時間 0.1 – 3600.0 (sec) ★16-6 = 0.0 (sec)時,關閉用水檢測機能。 ★使用用水檢測機能時,能有效幫助未用水或微少量用水時縮短變頻器進入休眠的時間。...
  • Page 80 16-A = 1 16-8 18-0 16-B time 18-7 16-5 16-6 time ★16-6 = 0.0 (sec)時,關閉用水檢測機能。 ★使用用水檢測機能時,能有效幫助未用水或微少量用水時縮短變頻器進入休眠的時間。 ★若持續用水頻繁時,建議可將 16-6 用水檢測週期調長,以減少檢測次數,可避免恆壓 時壓力因用水檢測導致飄動或不穩之情形發生。 ★因向下用水檢測機能動作時,會使頻率依據 16-B 用水檢測減速時間減速,若仍持 續用水狀況下,壓力會因轉速降低導致下降後立即提高轉速補回(壓力回授是否低於(工 作壓力設定(18-0)-用水檢測壓力範圍(16-8))作判斷),過程中可能會造成短暫壓力飄動或 不穩,16-8 用水檢測壓力範圍應適當調整,避免壓力飄動過大問題產生,如微量漏水於 減速過程中導致壓力調降,則視先到達休眠頻率或壓力是否低於(工作壓力設定(18-0)- 用水檢測壓力範圍(16-8))來決定進入休眠會再加速。 優點 缺點 1. 於用水檢測過程中壓力能永遠保持在目標壓 1. 如揚程過高導致當微量用水或無用水情 用水檢測 力之上,針對較嚴苛與精準的應用場合 況下工作頻率偏高,向上用水檢測效果 方向向上 會受限制較難進入休眠。 2.
  • Page 81 (12):16-9 高低壓與雙泵浦單機運轉故障自動復歸時間 0 – 200 min 16-9 = 0 (min)時,關閉故障自動復歸功能 當泵浦發生 Hi-p 或 Lo-p 時,泵浦跳機停止運轉,當時間超過 16-9 設定時間後,泵浦會 自動再啟動打水。 若雙泵浦運轉發生 1BrE 警告(單機運轉,另一台故障)時,在 19-3 交換時間內,且時間 超過 16-9 設定後,1BrE 警告會自動消失,直到本次交換時間後,才會再做 1BrE 警告 偵測。...
  • Page 82 (13):17-0 比例增益(P) 0.0 – 10.0 rate 17-1 積分時間(I) 0.0 – 100.0 sec 17-2 微分時間(D) 0.00 – 10.00 sec 過衝量 18-0:命令值 穩態誤差 壓力回授值 安定時間 參數調整參考: 調大影響 調小影響 註 (優)增快恆壓控制反應 (優)降低震動 調整 比例增益(P) (缺)太大容易產生回水震動 (缺)反應慢 安定時間 (優)降低誤差值 (優)反應變快 調整 積分時間(I) (缺)恆壓控制反應變差 (缺)誤差變大 穩態誤差...
  • Page 83 (14):17-3 輸出濾波時間(O) 0.0 – 2.5 sec PID 調整後輸出 PID 調整前輸出 參數設定可降低水壓忽大忽小或表頭指針左右震盪問題。 參數設定太大也會降低恆壓控制反應。 (15):17-4 回授調整(F) 0.00 – 10.00 rate 17-5 回授種類 0000:0 ~10V 0001:4 ~ 20mA 17-6 回授濾波 1 – 100 (base on 4ms) 面板顯示 回授訊號 準位過高 回授訊號 準位過低 回授訊號 當壓力回授訊號與變頻器讀取有一偏移量,可透過此參數調整。 例如回授訊號與面板讀取值有如上圖情況:可適用此參數調整。...
  • Page 84 (16):17-7 漏水檢測單位時間 0.0 – 10.0 sec 17-8 漏水檢測再啟動壓力變化量 0.01 - 2.50 Bar 17-9 漏水再啟動壓力誤差範圍 0.01 - 2.50 Bar 17-7 = 0.0 (sec)時,關閉此功能。 當泵浦休眠停機時,若管路有漏水導致壓力會隨時間而下降,在每一次 17-7 檢測時間 內,若壓力變化大於 17-8 漏水檢測再啟動壓力變化量時,泵浦會再啟動打水。...
  • Page 85 Case2 17-8 18-0 ∆P1 ∆P2 ∆P3 17-7 17-7 17-9 17-7 time time ∆P1 < 17-8 ∆P2 < 17-8 ∆P3 < 17-8 17-7 = 0.0 (sec)時,關閉此功能。 當泵浦休眠停機時,若管路有漏水導致壓力會隨時間而下降,在每一次 17-7 檢測時間 內,若壓力變化小於 17-8 漏水檢測再啟動壓力變化量時,變頻器會繼續保持休眠狀態, 直到單位時間內壓力變化大於 17-8 漏水檢測再啟動壓力變化量,或壓力誤差範圍超過 17-9 漏水再啟動壓力誤差範圍,泵浦會再啟動打水。 適當調整 17-7/17-8/17-9 漏水檢測相關參數,可改善用水系統因漏水時壓力下降,導致 泵浦頻繁啟動停止之情況。 漏水檢測機能僅在設定為單泵浦有效。...
  • Page 86 (17):18-0 工作壓力設定 0.10 – 25.50 Bar 18-1 最大壓力設定 0.10 – 25.50 Bar 18-2 最小壓力設定 0.10 – 25.50 Bar 18-1:最大壓力限制 18-0:工作壓力設定 實際壓力回授值 18-2:最小壓力限制 time 在 PID 的控制之下壓力會介於最大壓力(18-1)與最小壓力(18-2)之間。 (18):18-0 工作壓力設定 0.10 – 25.50 Bar 18-3 高壓警告時間 0.0 – 600.0 sec 18-4 高壓停機時間 0.0 – 600.0 sec 18-1:最大壓力限制...
  • Page 87 (19):18-0 工作壓力設定 0.10 –25.50Bar 18-5 低壓警告時間 0.0 – 600.0 sec 18-6 低壓停機時間 0.0 – 600.0 sec 18-1:最大壓力限制 實際回授壓力 18-0:工作壓力設定 18-2:最小壓力限制 time 沿(16-3)減速時間停機 time Lo-p T1 < (18-5 低壓警告時間); T1 後重新計數 T2 = (18-6 低壓警告時間);面板閃爍並顯示 Lop T3 = (18-7 低壓停機時間);面板閃爍並顯示 Lo-p...
  • Page 88 (20):18-7 恆壓休眠時間 0.0 – 120.0 sec 18-8 恆壓誤差範圍 0.00 – 5.00 Bar 18-8 18-0 time 18-7 16-4 time |(18-0) - | < 18-8 恆壓停機目的為節省能源。 (21):18-9 高低壓故障自動復歸次數 0 – 999 min 1.) 當 18-9=0:發生高低壓故障時,變頻器依 16-9 復歸時間無限次數自動復歸。 2.) 當 18-9=1~999:當高低壓故障自動復歸次數超過 18-9 設定之次數後,變頻器即不再自 動復歸,若變頻器...
  • Page 89 (24):19-0 單/雙泵浦與主副機設定 0:單泵浦 1:多泵浦-主機 2:多泵浦-副機 1 3:多泵浦-副機 2 4:多泵浦-副機 3 19-2 多 泵 浦 同 步 選 擇 0:關 閉 1:壓力設定及 Run/Stop 同步 2:壓力設定同步 3:Run/Stop 同步 19-3 交換時間 0 – 240 hour 19-4 偵測時間 0 – 30.0 sec 18-8 18-0 19-4 time time...
  • Page 90 說 明: A:雙泵浦啟動,主機先啟動打水,副機停機待命,進入恆壓運轉。 B:用水量變大,主機運轉頻率升高,若水壓未到達恆壓誤差範圍內,且時間未超過 19-4 偵測時間,副機仍停機待命。 C:若超過 19-4 偵測時間,主機告知副機啟動輔助打水,主、副機共同運轉後即可維持系 統恆壓,若用水量減少則副機運轉頻率下降。 D:當用水量再變小,透過用水檢測功能,副機運轉頻率則再下降,當用水量減少至單一 泵浦運轉即可應付時,僅主機運轉即可維持恆壓,副機則會停機休眠(雙泵浦副機休 眠條件於 19-6 與 19-7 說明) ,剩下主機運轉。 19-3 雙泵浦運轉時,若運轉時間超過 19-3 交換時間後,主機與副機角色對調,交換運轉。 19-4 當回授訊號低於 18-8,主機立即啟動,副機啟動條件為壓力低於 18-8 且時間大於 19-4 時,副機啟動輔助主機打水 註:當使用雙泵浦 19-0≠0 時,兩台變頻器參數 19-0 不可同時設為 1 或同時設為 2, 同時亦需調整 19-5=200 且微調 17- 4,使兩台變頻器的回授值為相同值。 (25):19-1 壓力傳送器最大壓力...
  • Page 91 (28):20-0 運轉命令來源 0 : 按鍵面板 1 : 外部端子 1.) 20-00 = 0 變頻器為按鍵面板運轉控制。 2.) 20-00 = 1 變頻器為外部端子運轉控制時,可以按面板上之 Stop 鍵緊急停止。 (29):20-1~20-5 S1~S5 端子功能設定 0 : 正轉指令 1 : 外部急停 A 接點 2 : 外部遮斷 3 : RESET 指令 4 : 控制信號切換 5 : 通訊中控制信號切換...
  • Page 92 (30):20-6~7 多機能輸出接點控制 : 20-6 : RELAY1(TM2 之 R1C,R1B,R1A 接點) 20-7 : RELAY2(TM2 之 R2B,R2A 接點) 0 : 運轉中 1 : 故障接點 2 : 自動再啟動 3 : 瞬間停電 4 : 外部急停 5 : 自由運轉停止 6 : 馬達過載保護 7 : 變頻器過載保護 8 : 高低壓警告 9 : 電源投入...
  • Page 93 多機能類比輸出之控制 (32):20-A 多機能類比輸出之種類選擇 : 0 : 變頻器輸出頻率 1 : 變頻器設定頻率 2 : 變頻器輸出電壓 3 : 變頻器直流電壓 4 : 變頻器輸出電流 5 : 變頻器 PID 之 FEEDBACK 訊號 20-B 多機能類比輸出之增益控制 = 0~200% 端子臺(TM2)多機能類比輸出端子為一 0~10Vdc 之類比輸出,其輸出種類由 20-A 決 定,而當外部電表或其他週邊設備有誤差時,可利用 20-B 調整。...
  • Page 94: 第五章 故障排除及保養

    第五章 故障排除及保養 5.1 故障指示及對策 5.1.1 無法手動復歸且無法自動復歸之故障 顯 示 內 容 異 常 原 因 對 策 於產生干擾之電磁接觸器之激磁線圈 程式異常 外部雜訊干擾 並聯 RC 突波吸收器 EEPROM 異常 EEPROM 故障 更換 EEPROM 停機中偵測到 -OV- 偵測線路故障 變頻器送修 電壓過高 1. 電源電壓過低 1. 檢查電源電壓是否正常 停機中偵測到 -LV- 2. 限流電阻(R1)或保險絲燒斷 2.
  • Page 95: 可手動復歸但不可自動復歸之故障

    顯 示 內 容 異 常 原 因 對 策 壓力低於設定之失壓比例且超過 1. 降低最小壓力限制的壓力值 失壓故障 失壓檢測時間 2. 檢查壓力計或實際水量 5.1.3 可手動復歸但不可自動復歸之故障 顯 示 內 容 異 常 原 因 對 策 停機中偵測到 1. 偵測線路故障 1. 檢查配線確認是否受到干擾 過電流 2. CT 訊號線連接不良 2. 變頻器送修 馬達過載...
  • Page 96: 一般故障檢查方法

    5.2 一般故障檢查方法 異 常 現 象 檢 查 要 點 處 理 內 容 電源電壓是否有送入 L1 (L)、L2、L3 (N) ‧電源是否有投入‧將電源先斷電後再送電一次 端(充電指示燈是否亮)嗎? ‧電源電壓等級確認‧端子螺絲是否鎖緊 輸出端子 T1、T2、T3 是否有電壓輸出嗎? ‧將電源先斷電後再送電一次 負荷是否過重,造成馬達堵死嗎? ‧減輕負荷使馬達可以運轉 馬達不運轉 變頻器有異常發生嗎? ‧參考故障指示排除處理配線檢查並更正。 正轉或反轉運轉指令有下達嗎? ‧類比頻率輸入信號配線是否正確 類比頻率設定值有輸入嗎? ‧頻率輸入設定電壓是否正確 運轉模式設定值正確嗎? ‧由數位操作運轉 馬達運轉 輸出端子 T1、T2、T3 配線正確嗎? ‧要與馬達之...
  • Page 97 附錄. 壓力(Pressure) 壓力之定義為單位面積上所受力之大小。若一大小為F之力,作用於大小為A之面積上, 則此面積所承受之壓力P為 正向力 壓力 = 受力面積 / Cm 壓力常用之單位在公制為 ,亦即每平方公分上作用多少公斤力,常簡略以 / Cm 表示。英制則為 P.S.I,亦即每平方英吋上作用多少磅之力,二者間之換算關係 約為: / Cm = 14.22 P.S.I 或 1P.S.I = 0.07 / Cm 1 Bar = 1 00 kPa = 1.02 / Cm 14.5 P.S.I 壓力單位換算...