OUTPUT DATA
Output power at nominal inputs
Derating
Output voltage
Voltage wave form
Crest factor
Output frequency (synchronised to mains)
Transfer time
Overload protection
BATTERY
Type of battery
Voltage
Typical backup time at half power
Typical backup time at full power
Charging method
Charging time
Charge current
Average charging voltage
Protection
Revision 1
600 W / 1000 VA max. at +40 °C
+40...+60 °C, 10 W / K
230 V AC
Sine
3:1
Auto select for 50/60 Hz
47 Hz ~ 55 Hz for 50 Hz nominal;
56 Hz ~ 65 Hz for 60 Hz nominal
Blackout 3 ms typical, Brownout 1 ms,
battery mode to normal mode: 1 ms typical
Overload alarm level 100 % ~ 120 %,
Overload shutdown level 120 % ~ 190 %
1x BP-2480 (Cyclon), 24 V/ 8 Ah, 12 cells
24 V DC
500 VA / 300 W: ca. 14 Min. bei +20 °C
1000 VA / 600 W: ca. 4.5 Min. bei +20 °C
Smart puls charging with 2 charging modes:
Quick charging,
Trickle charging, at 90 % battery capacity
App. 5 hours for 90 %, at 230 V AC and +25 °C
2.5 A max.
Quick charging mode: 28.1 V max.
Trickle charging mode: 26.2 V...28.1 V
Thermal protection, overcurrent protection and
overcharging voltage protection