Connecting Data Cables - Pepperl+Fuchs RocketLinx ICRL-U-8M12-G60 Manual

Table of Contents

Advertisement

ICRL-U-8M12-G60 Manual
Installation

3.4. Connecting Data Cables

Use the following guidelines when connecting the data cables.
Shielded CAT5e cable or better.
SF/UTP cables as per ISO/IEC 11801:2002.
Shielded D-coded, 4-pin M12 connectors.
Keep the length of the data cables as short as possible.
When using copper cables, provide a sufficient separation between the power supply cables and the data
cables.
Verify that power supply cables and data cables do not run parallel over longer distances, and that ideally
they are installed in separate cable channels. If reducing the inductive coupling is necessary, verify that the
power supply cables and data cables cross at a 90° angle.
Seal all unused connections and ports with the provided plastic protection screws.
Make sure the cable shielding is connected to the M12 plug thread.
Note: The torque for tightening the protection screws on the device is 5.3 lb- in (0.6 Nm).
D-Coded, M12
Pin
Signal
1
Tx+
2
Rx+
3
Tx-
4
Rx-
15