Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model G2 Sprinkler Guard, Model WS-2 Shield, and
Model WSG-2 Sprinkler Guard with Shield
Series ELO-231, ELO-231B, and ELO-231FRB Sprinklers
General
Description
The Model G2 Sprinkler Guard (Ref.
Figure 1) is designed for use with
Series
ELO-231,
ELO-231B,
ELO231FRB Sprinklers that may be
located in areas that make them sus-
ceptible to mechanical or physical
damage.
The WS-2 Shield (Ref. Figure 2) is de-
signed to shield pendent sprinklers
from water spray of higher elevation
sprinklers (e.g., rack storage sprinkler
installations). When the WS-2 Shield
is used with the Series ELO-231,
ELO231B, or ELO-231FRB Pendent
Sprinklers, the assemblies become
Pendent Intermediate Level Sprin-
klers intended for use in fire sprinkler
systems designed in accordance with
the standard installation rules recog-
nized by the applicable Listing agen-
cy (i.e., UL Listing is based on NFPA
requirements).
The Model WSG-2 Sprinkler Guard
with Shield (Ref. Figure 3), in addition
to providing protection from mechani-
cal or physical damage, shields the
upright sprinkler from water spray of
higher elevation sprinklers (e.g., rack
storage sprinkler installations). When
the WSG-2 is used with the Series
ELO-231, ELO-231B, or ELO-231FRB
Upright Sprinklers, the assemblies
become Upright Intermediate Level
Sprinklers intended for use in fire
sprinkler systems designed in accor-
dance with the standard installation
rules recognized by the applicable
Listing agency (i.e., UL Listing is based
on NFPA requirements).
The G2, WS-2, and WSG-2 are a re-
designation for the Central G2, WS-2,
and WSG-2.
notice
The Model G2 Sprinkler Guard, WS-2
Shield, and WSG-2 Sprinkler Guard
with Shield described herein must be
Page 1 of 4
installed and maintained in compli-
ance with this document, and with the
applicable standards of the National
Fire Protection Association, in addi-
tion to the standards of any authori-
ties having jurisdiction. Failure to do
so may impair the integrity of these
or
devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or manufac-
turer should be contacted relative to
any questions.
Technical
Data
Approvals
UL and C-UL Listed. FM Approved.
(Refer to Table A)
Finishes
Red Painted and Zinc Coated
Physical Characteristics
Welded assembly fabricated from
carbon steel
Design Criteria
In accordance with the requirements
of the NFPA, sprinkler guards shall be
listed. Guards are only listed for use
with specified sprinklers; therefore,
the G2 and WSG-2 must only be used
with the Series ELO-231, ELO-231B,
and ELO-231FRB Sprinklers shown in
Table A.
MAY, 2009
G2
WS-2
WSG-2
TFP782