Setpoints
Use
and
buttons to move or change value.
Basic settings
Setpoint
Setpoint name
code
B01
Nominal Voltage Ph-N
B02
Nominal Voltage Ph-Ph
B03
Nominal Frequency
B04
Connection Type
B05
Units Format
B07
Zero Power Mode Delay
B08
Light Tower Mode
B09
Nominal RPM
Generator protections
Setpoint
Setpoint name
code
G01
Generator Overvoltage Shutdown
G02
Generator Undervoltage Shutdown
G03
Generator Overfrequency Shutdown G04
G04
Generator Underfrequency Shutdown
To apply all changes return to the main setup menu and restart the controller by pressing the
Alarms and Events
Events
Manual Start
Remote Start
Manual Stop
Remote Stop
Auto On
Auto Off
Power On
Island Operation
ECU
For ECU configuration use PC software NanoEdit. For more details see InteliNano AMF Reference Guide.
Technical data
Power supply range
6-36 VDC
Power supply drop-out immunity
100 ms
Power consumption
35 – 295 mA
Zero Power Mode consumption
52 - 344 µA
Binary outputs (up to 4)
Low current outputs (2)
500 mA
High current output (2)
6 A (long term) / 10 A (short term)
Total output current
10 A (long term) / 16 A (short term)
Analog inputs (up to 3)
Galvanic insulation
Not insulated
Electrical range
0 - 2500 kΏ
Resolution
0,1 Ώ
Precision
2 % ± 3 Ώ
Charging alternator preexcitation circuit
Excitation current
100 mA
Charging fail threshold
80 %
InteliNano-NT MRS, SW version 1.4, ©ComAp – March 2013
InteliNano-NT-MRS-1.4-Fast User Guide.pdf
4
Start
button to select setpoint or confirm changes and
Setpoint
code
80 – 480 V
E01
80 – 600 V
E02
E03
50 Hz (1), 60 Hz (2)
Mono Phase (1), SplitPhase (2),
E04
3Ph3Wire (3), 3Ph4Wire (4)
E05
Metric unit format (1), US unit
E06
format (2)
E07
0-360 min
E08
Disable (1), Enable (2)
E09
100-4000
E10
G02
– 200 %
0 -
G01
%
– 130 %
G03
0 –
%
Warnings
Warning Maintenance
Low Battery
Low Fuel Level
External Warning 1
External Warning 2
External Warning 3
ECU Communication Error
Operating temperature
Operating humidity
Protection degree (front panel)
Storage temperature
Binary inputs (up to 6)
Input resistance
Closed contact voltage
Open contact voltage
Generator/Mains measurements
Measurement input
Measurement type
Voltage range
Max. measured voltage
Voltage accuracy
Frequency range
Frequency accuracy
Stop
button to go back.
Engine parameters and protections
Setpoint name
Prestart Time
Maximum Cranking Time
Cooling Time
Oil Pressure Shutdown
Coolant Temperature Shutdown
Battery Undervoltage
Warning Maintenance
Oil Pressure Starter Disengagement
Choke Time
Minimal Stabilization Time
Stop
button.
Shutdowns
Emergency Stop
Overspeed
Underspeed
Low Oil Pressure
High Coolant temperature
External Shutdown 1
External Shutdown 2
External Shutdown 3
GCB Fail
Generator Overvoltage
Generator Undervoltage
Generator Overfrequency
Generator Underfrequency
Generator CCW Rotation
Start Fail
Stop Fail
Battery Flat
-20... 70 °C
95% non-condensing (IEC/EN 60068-2-30)
IP65 with GASKET 4x405 only
IP50 without gasket
-30... 80 °C
1,5 kΏ
<2 V
>3,5 V
3ph generator voltage
True RMS
480 V Ph-Ph (277 V Ph-N)
340 V Ph-N
1%
40 – 70 Hz
1 %
0-600 s
0-60 s
0-3600 s
0-10 Bar
0 -150 °C
8 – 40 V
0 – 10000 h
Disable (1), Enable (2)
0 – 3600 s
1 – 300 s