Noritz ecoTOUGH NRC98-DV-NG Installation Manual page 18

Condensing tankless gas
Hide thumbs Also See for ecoTOUGH NRC98-DV-NG:
Table of Contents

Advertisement

Vent Pipe Installation (When supplying combustion air from the indoors (SV, non-direct vent))
When installing this water heater in an area with a large amount of lint such as a commercial Laundromat,
direct-vent ("-DV") system must be used. The "-SV" configuration (using an SV conversion kit) is prohibited.
• Disconnect power and turn ON dip switch 3 if combustion air will be supplied from the
indoors as illustrated to the right. Refer to page 30 for the location of the dip switch bank.
• SV Conversion kit #SV-CK-3 is required for the air intake.
Failure to perform the above 2 steps could result in a fire or explosion causing
property damage, personal injury or death.
Refer to the instructions provided with the conversion kit for additional details.
Horizontal Vent Termination- PVC/CPVC Materials Only
Exhaust
Intake
SV Conversion Kit
Accessory
(#SV-CK-3)
Inlet screen
90 Elbow
Vertical Vent Termination- PVC/CPVC Materials Only
Exhaust
Intake
SV Conversion Kit
Accessory
(#SV-CK-3)
Inlet screen
90 Elbow
18
DANGER
WARNING
Hanger
Straps
Slope vent
Upwards
**1' (0.3m) Minimum
* Not supplied with water
heater, order separately.
**1' (0.3m) Minimum
recommended, but not required.
Insert Bird
Screen* in
End of 90
Elbow
Storm
Collar
Roof
Flashing
Firestop/Support
Support
Firestop
Hanger
Strap
Slope vent
Upwards
**1' (0.3m)
Minimum
* Not supplied with water
heater, order separately.
**1' (0.3m) minimum
recommended, but not required.
A tee, the PVT-HL termination may be used for the vent
3" Min.
termination. It is not necessary to use bird screens with
the PVT-HL termination.
Terminate at least 12" (300mm) above grade or above
snow line.
Terminate at least 7' (2.1m) above a public walkway,
Insert Bird
Screen* in
6' (1.8m) from the combustion air intake of any appliance,
Each End
and 3' (0.9m) from any other building opening, gas utility
of Tee
meter, service regulator etc.
Terminate at least 3' (0.9m) above any forced air inlet within
10' (3m) , 4' (1.2m) below, 4' (1.2m) horizontallyfrom or
1' (0.3m) above any door, window, or gravity air inlet into any
building per National Fuel Gas Code ANSI Z223.1/NFPA 54.
Slope the horizontal vent 1/4" upwards for every 12" (300mm)
toward the termination.
Use a condensation drain if necessary.
In the Commonwealth of Massachusetts a carbon monoxide
detector is required for all side wall horizontally vented gas
fuel equipment.
Please refer to Technical Bulletin TB 010606 for full installation
in structions.
Terminate at least 6' (1.8m) from the combustion air
intake of any appliance, and 3' (0.9m) from any other
building opening, gas utility meter, service regulator etc.
Enclose exterior vent systems below the roof line to limit
condensation and protect against mechanical failure.
When the vent penetrates a floor or ceiling and is not
running in a fire rated shaft, a firestop and support is
required.
When the vent termination is located not less than
8' (2.4m) from a vertical wall or similar obstruction,
terminate above the roof at least 2' (0.6m), but not
more than 6' (1.87m), in accordance with the National
Fuel Gas Code ANSI Z223.1/NFPA 54.
Provide vertical support every 3' (0.9m) or as required
by the vent pipe manufacturer's instructions.
A short horizontal section is recommended to prevent
debris from falling into the water heater.
When using a horizontal section, slope the horizontal
vent 1/4" upwards for every 12" (300mm) toward the
termination to drain condensate.
* Dip switch No.3 is turned on.