Page 5
Nothing contained in this document shall increase the liability or extend the warranty obligations of the manufacturer Arcteq Relays Ltd. The manufacturer expressly disclaims any and all liability for any damages and/or losses caused due to a failure to comply with the instructions contained herein or caused by persons who do not fulfil the aforementioned requirements.
3.1 Unit features AQ-101S is a multipurpose arc flash protection unit and it can be applied to a variety of applications that require a large amount of data communication. It can be used on its own as a stand-alone unit, or it can be a part of a more complex arc protection system through a binary bus.
Instruction manual Version: 2.01 3.2 Dimensions and installation AQ-101S can be either door-mounted or panel-mounted in a standard 19 inch rack. The unit's dimensions (without cards) are as follows: • Height: 157 mm (6.18 in) • Width: 50 mm (1.97 in) •...
Page 11
Version: 2.01 The following image illustrates how a unit is installed into a cut-out. Please note that as AQ-101S is narrower than the unit in the image, it is connected to the cut-out panel by a single screw on both the top and the bottom of the front panel instead of the two depicted below.
Please note that the latching (or non-latching) of trip relays T1 and T2 is determined with the DIP switch (SW1:6). The trip relay T3 is always latched. The binary output BO1 is always non-latched! 3.4 Wiring Figure. 3.4 - 5. Wiring diagram for AQ-101S. Station battery AQ-101S Uaux L>...
4 Operation and configuration 4.1 LED indicator functions The AQ-101S unit has seventeen (17) indication LEDs. Apart from the "Power" and "Error" LEDs, the user can write their own identifications for each of the remaining LEDs on the text insert located in the transparent pocket next to the LEDs.
For detailed instructions on each of the available schemes please refer to the AQ-SAS™ booklet (can be found at arcteq.fi/downloads/). Please note that there are four booklets: two are for schemes based on IEC standards (MV and LV versions) and the other two for schemes based on ANSI standards (MV and LV versions).
Page 18
The binary input BI3 receives overcurrent information from the incoming feeder of a connected AQ-110P unit. The binary output BO1 sends light information to the incoming feeder of a connected AQ-110P unit when AQ-101S detects any arc fault.
In order to indicate the breaker's precise location, its position information is sent to the AQ-101S unit via the BI1 (main busbar) or BI2 (reserve busbar) binary input channel. The T1 trip contact is responsible for tripping the breaker. T3 gives synchronous information on the trip alarm.
-101S Instruction manual Version: 2.01 8 Connections The figures below depict the connections of AQ-101S. Please note that the SF relay is in the de- energized position. Figure. 8 - 26. Rear terminals of AQ-101S. 8.1 Outputs 8.1.1 Trip relays This unit has two (2) integrated trip relays for tripping circuit breakers, namely T1 and T2.
8.2 Inputs 8.2.1 Arc sensor channels AQ-101S has four (4) arc point sensor channels: S1, S2, S3 and S4. You can connect a maximum of three (3) arc point sensors to each channel. For more information on sensors, please refer to the "Arc sensors" chapter as well as to the AQ-0x instruction booklet which can be found on Arcteq's website (https://www.arcteq.fi/downloads/).
2. Connect one of the test set's outputs to a strong camera flash to initialize the flash and to configure the set's timer to start simultaneously with the flash. 3. Connect one of the AQ-101S unit's trip outputs (T1, T2, T3) to a test set input and configure the input to stop the timer.
Need help?
Do you have a question about the AQ-101S and is the answer not in the manual?
Questions and answers