PRO-2200 Remote Enclosure—PRO22ENC3
Power Supply
DO NOT USE POWER SUPPLY TO POWER LOCKS
- 12 VDC 2 amp continuous power limited output with backup battery charging and
battery supervision.
- A 16.5 VAC 20 VA wall transformer is provided.
- Requires 115 VAC/60 hz.
- Maximum battery charge current .5 amp.
- AC on LED.
- AC Fail supervision.
- Low Battery Supervision (form "C" contacts).
- Short circuit and thermal overload protection.
Note: All power connection should be made with 18 gauge or larger wiring.
LED Diagnostics
AC LED
ON
OFF
ON
OFF
Backup Power Supply
• Automatic Switch over to standby battery when AC fails (zero voltage drop).
• 4.0 amp hour sealed rechargeable battery (BAT-3).
• Backup time: 1 hr. at maximum 2 amp current draw (longer for configurations with lower
current draw).
Cables Supplied
• Power On Light assembly.
• Tamper Switch assembly - Use of Tamper Switch is required by UL294.
Maintenance
• Replace the 12V 4 amp hour battery every 2 to 2.5 years.
• Oil the hinges on the door every 12 months.
Operating Parameters
• Temperature: 35° F to 110° F (2° C to 43° C).
• Operating Humidity: Up to 85% non-condensing.
DC LED
ON
Normal operating conditions
ON
Loss of AC, standby battery supplying power
OFF
No DC output
OFF
Loss of AC, Discharged or no Standby battery. No DC output.
Installation Guide