All acoustic testing conducted at 230 Volt, 50Hz and undertaken at the EBM- Papst Acoustic Laboratories in Connecticut USA during August 2014 MOTOR Please contact Airius for full Noise Testing Report Single Phase Electrically commutated, variable speed 92% efficient motor...
However it is permanently mounting in the ceiling. not imperative. For Cooling the Airius fan should be located to suit client’s require- MAINTENANCE ments. Suggested locations are from just under the ceiling or closer to the floor to ensure suitable air-cooling flow.
Page 4
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC CHAIN HUNG (STRAIGHT) PLUG NOT SUPPLIED To Control Module Safety chain/ Unistrut or Ceiling Beam cable secured Cord Secured Receptacle Rated Chains should be rated @ 75 Kgs each 240 VAC (Not supplied).
Page 5
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC CHAIN HUNG (ANGLED) PLUG NOT SUPPLIED To Control Module Safety chain/ Unistrut or Ceiling Beam cable secured Cord Secured Receptacle Rated 240 VAC 240 v Plug Chains should be rated @ 75 Kgs each (single phase) (Not supplied).
Page 6
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC PEARLINK Reduce installation cost & control your Airius fan system over 2.4Ghz WiFi DISTRIBUTED COMFORT FEATURES The PearLink control system offers total fan control from a Interface is web-based (Chrome/Firefox), iOS, or Android »...
Page 7
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC Housing: PC/ABS, Off white (cool gray 2c) Mounting: Factory installed at time of ordering. Power Consumption Idle: 16mA TX/RX: 200mA AIRIUS FAN SYSTEM Wi-Fi Characteristics 802.11b/g/n 2.4 GHz...
This is your command-and-control portal for the Airius fans at your facility. You can use the web based dashboard or the the Airius PearLink mobile app, available for both iOS and Android, to operate fans to fully control the air movement in a room.
1.5-1.8 mts A.F.F. Preferably next to your existing thermostat. Open the Airius App and enter your email address and password to log in. You are now ready toprovision your devices. Note: the screen shots are from an Android device and might vary slightly for iOS devices.
Page 10
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC > > Name the device Continue Enter the associated invoice number > > Enter the ceiling height where the Review the information and select Select, “Add new device and apply most recent profile”...
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC DEVICE CONTROL The PearLink app allows for individual and group fan control. PearLink will monitor the air temperature at the fan and at the floor to provide a delta temperature. The humidity and air temperature will be logged and viewed within the app. This data can be exported as a csv file.
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC NETWORK MIGRATION If you need to change your Wi-Fi network name or password for any reason, you must follow this process. If the name or password is changed before this step, the devices cannot be connected to. The only way to recover them is to revert back to the old network name and password.
Page 13
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC BMS CONTROL WIRING GENERAL NOTES 0-10 V signal allows infinitely variable open loop speed control Connecting the red and yellow leads will allow EC fans to operate Blue...
Page 14
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC POTENTIOMETER EC (0-10V) NON-POWERED SPEED CONTROLLER FEATURES Input Voltage: 10VDC Output Voltage: 0-10VDC OPERATION Rotating the dial will change the output voltage from 0VDC to 10VDC and change fan speed. The push button is used for on/off control.
25mm SPECIFICATIONS CONTROLLER DESCRIPTION Operating voltage 24V DC ONLY (By Others) Overview The Airius Touch Screen Controller is a programmable Mounting Surface mount backbox option room controller ideal for managing Airius EC fans. Display 3.5” Resistive touch-screen The unit has no on-board inputs & outputs, but is...
Page 16
Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC INPUT OUTPUT MODULE FOR AIRIUS TOUCH SCREEN CONTROLLER Fire Alarm Connection (By Others): UI1 Compact Modbus RTU input/output module for the Airius room controller Indoor Secondary Temperature Sensor Real-time clock Connection: U16...
Page 17
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC CONNECTIONS M/TIO DESCRIPTION General Triac Outputs 2 triac outputs are provided with fl exible confi guration options, M/TIO modules provide a compact input/output solution for Modbus allowing control of on/off thermoelectric (PWM) or fl oating RTU master controllers.
Page 18
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC BLUE BLUE YELLOW EC Fan YELLOW EC Fan BLUE BLUE EC Fan EC Fan YELLOW YELLOW BLUE BLUE EC Fan EC Fan YELLOW YELLOW BLUE BLUE 9 10...
Page 19
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC AIRIUS TOUCH SCREEN CONTROLLER WITH FIRE ALARM INPUT (BY OTHERS) AND EXT TEMP SENSOR - 4 FANS BLUE EC Fan YELLOW BLUE EC Fan YELLOW BLUE EC Fan...
Page 20
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC AIRIUS TOUCH SCREEN CONTROLLER WITH FIRE ALARM INPUT (BY OTHERS) WIRING DIAGRAM - 4 OR 8 FANS OR GROUPS OF AND EXT TEMP SENSOR - 8 FANS BLUE...
Page 21
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC STANDARD WALL BOX INSTALLATION Front Back Exterior Fit base unit in fl ush-mounted box. Fasten metal frame to wall box with two screws*. max 2.6 mm max 3.5 mm Interior max 6.9 mm...
AP-60/EC-230V Product Information & Installation Guide AIR PEAR SERIES - Model 60/EC INSTALLATION TIPS 0.5 m 1.5 m +61 (2) 6608 2736 info@airius.com.au www.airius.com.au...
Need help?
Do you have a question about the AIR PEAR Series and is the answer not in the manual?
Questions and answers