Output Wiring - Relay Version; Spark Protection - Ametek Drexelbrook IntelliPoint RF RNL Series Installation And Operating Instructions Manual

Point level switch
Table of Contents

Advertisement

RNLXX1 - IntelliPoint RF Series User's Manual
2.3
Input Wiring (Continued)
One 5A SPDT Alarm and One 5A SPDT Fault
2.4

Output Wiring - Relay Version

2.5

Spark Protection

M4 / 2.5mm Hex Drive
4
3
2
1
M3 / 2.5mm
Hex Drive
3
4
5
NO
C
NC
Alarm
Input and Relay Wiring / Customer Connections Side
One 5A DPDT Alarm
3
4
5
IMPORTANT
Ground Must be Connected for Proper Operation and Safety.
NO
C
NC
Alarm
The IntelliPoint RF series instrument is supplied with two
sets of contacts. The relay contacts can be used as one of the
following configurations depending on the RELAY #2 jumper
configuration (see Figure 2-3 and 2-4)
• One 5A SPDT alarm relay and one 5A SPDT fault relay.
• Two 5A SPDT alarm relays.
Applications involving insulating granulars and insulating
liquids may produce a static discharge that can damage the
electronics. The RF series instrument is supplied with
integral heavy-duty spark protection to prevent static
discharges from damaging the electronic circuits.
#8-32 / Phillips-Slotted
Drive
5
6
7
8
One 5A SPDT Alarm and One 5A SPDT Fault
1
L1
M3 / 2.5mm
Hex Drive
85 to 250 VAC
M5 / Slotted Drive
21 to 100 VDC
Ground Connection
Auto-Detecting
6
7
8
NO
C
NC
Fault
Figure 2-3
6
7
8
NO
C
NC
Alarm
10
2
3
4
5
6
3
4
5
6
L2
NO
C
NC
NO
NO
C
NC
NO
Relay #1
Relay #2
Alarm
Fault
Two 5A SPDT Alarms
3
4
5
6
NO
C
NC
NO
Alarm
Alarm
7
8
7
8
C
NC
C
NC
7
8
C
NC