Fedders C1018BBD Installation, Operation And Maintenance Manual

Fedders C1018BBD Installation, Operation And Maintenance Manual

Model c10 & c12 series — 1.5 thru 5 ton split system high efficiency air conditioner

Advertisement

Installation, Operation and Maintenance
MODEL C10 & C12 SERIES — 1.5 THRU 5 TON
Split System High Efficiency

Air Conditioner

REV. 9/22/04
23-23-0418N-003

Advertisement

Table of Contents
loading

Summary of Contents for Fedders C1018BBD

  • Page 1: Air Conditioner

    Installation, Operation and Maintenance MODEL C10 & C12 SERIES — 1.5 THRU 5 TON Split System High Efficiency Air Conditioner REV. 9/22/04 23-23-0418N-003...
  • Page 2: Table Of Contents

    TURNED OFF AT THE HOUSEHOLD SERVICE BOX TO AVOID THE POSSIBILITY OF SHOCK, INJURY, DEATH OR DAMAGE TO EQUIPMENT. REMOTE CONDENSER UNIT NOMINAL AIR CONDITIONER CAPACITY CHASSIS EFFICIENCY OPTION LEVEL D = STANDARD UNIT R-22 E = STANDARD UNIT R-407 F = HIGH &...
  • Page 3: Operation And Maintenance Instructions

    An additional waiting period will be required before restarting. 3. Since the air conditioner is located outdoors, it is exposed to all weather elements. Treat it with a good automobile paste wax twice a year (in the spring and fall).
  • Page 4: Evaporator & Condensate Drain

    EVAPORATOR & CONDENSATE DRAIN 1. Refer to the instructions supplied with the evaporator coil. 2. When installing the evaporator, refer to page 8 for condenser evaporator match-up. The evaporator should be installed in an insulated plenum of proper size to accommodate the coil, whether it be of the “A”...
  • Page 5: Replacement Application

    SPECIAL INSTRUCTIONS FOR REPLACEMENT APPLICATION When replacing an existing system, it is mandatory that a liquid line filter dryer (if not provided with the condensing unit) and a suction line filter, conforming to the dryer selection chart below, be installed in the new system if any of the original refrigerant-bearing components are to be used in the new installation.
  • Page 6: Field Charging Procedures

    FIELD CHARGING PROCEDURES SUPERHEAT CHARGING (for units with pistons) The superheat method is highly recommended for field charging or checking the existing refrigerant charge in a system. Because each installation is different in terms of indoor air flow, refrigerant line length, duct variations, etc., the factory charge may not be correct for every application.
  • Page 7 29.4 C SUPERHEAT CHARGING CHART FOR UNITS WITH PISTONS 80°F 30°F - 16.7°C 26.7°C 75°F 25°F - 13.9°C 23.9°C 70°F 20°F - 11.1°C 21.1°C 15°F - 8.3°C 10°F - 5.6°C 5°F - 2.8°C °C 12.8 15.6 °F LINE LIMIT – DO NOT ADD CHARGE IF POINT FALLS BELOW THIS LINE. Chart based on 350 to 400 CFM / ton indoor airflow and 50% relative humidity use on systems that cool with fixed restrictor.
  • Page 8: Air Handler & Evaporator Match-Ups

    AIR HANDLER & EVAPORATOR MATCH-UPS AIR HANDLER CONDENSER MODEL MODEL NUMBER NUMBER C1018B A24B1 C1024B A24B1 C1030B A36B1 C1036B A36B1 C1042B A42B2 C1048B A48B2 C1060C A60B1 C1218B A24B1 *C1224B *A30B1 C1230B A36B1 C1236B A36B2 C1242C A48B2 C1248C A48B2 C1260C A60B1 * For C1224B only, use LOW speed setting on Air Handler.