Hardware installation
4.2.2

Installation in PRIMECENTER/DataCenter Rack

For installation in a PRIMECENTER/DataCenter rack, the following parts are
required:
– Support bracket
– one support system on the left and one on the right
I
General information is provided in the Technical Manual for the
PRIMECENTER and/or DataCenter Rack.
Fitting the support bracket
When mounting the left telescopic rail in the PRIMECENTER/DataCenter Rack,
the supplied support bracket must first be mounted on the rear left support
upright flush with the bottom edge of the device.
Figure 3: Fitting the support bracket
Ê Position the support bracket at the corresponding height on the rear left
support upright, (place knob in the corresponding hole and secure it as
described in the Technical Manual for the rack in question.
RX200 S5
Installing/removing the server in/from the rack
Operating Manual
43