NORMAL - Only AC POWER is illuminated green.
All other indicators are off. LCD display will read SYSTEM ALL
NORMAL.
WHEN AUDIBLE DEVICES ARE SOUNDING -
FOR AN ALARM
1. Evacuate the protected area
2. Notify the monitoring service and/or the Fire Department immediately. Tell them briefly what happened and what your current status is.
Phones: ________________________________________
3. If the Fire Department is responding, be prepared to provide directions to arriving firefighters.
FOR TROUBLE, SUPERVISORY, AND EMERGENCY ALARMS
1. Notify the monitoring service and/or applicable first responders if this panel is connected to either one, and tell them what is happening.
2. Silence audible devices by unlocking and opening the panel and pressing the ACKNOWLEDGE/STEP button. The applicable indicator will
remain illuminated. Contact authorized service personnel immediately! (See Below).
DO NOT ALLOW TROUBLE CONDITIONS TO REMAIN LOGGED IN THE SYSTEM. THE PROTECTION THE
SYSTEM OFFERS HAS BEEN COMPROMISED OR ELIMINATED, WHEN A TROUBLE CONDITION EXISTS.
To return to normal after an alarm
1. Do not enter the protected area until safe to do so.
2. Clear all initiating devices. Smoke detectors will not reset if there is
still smoke in the area.
3. Reset the control panel (PRESS the RESET button).
Power failure or brownout
If AC power drops too low or fails, AC POWER indicator will extinguish,
the system TROUBLE indicator will turn on yellow, and the panel
buzzer and any other audible trouble devices will sound. Contact
authorized service personnel immediately. See below.
In the event of trouble, contact the
local Notifier Service Representative
Name: _____________________________________
Company: __________________________________
Address: ___________________________________
Telephone Number: __________________________
NFW-100X Series Fire Alarm Control Panel
Operating Instructions
Fire Department
PANEL KEY - The key to open the panel can be found at the following
location:
________________________________________________________
_____________________________________________
Monitoring Service
WARNING!
Manual activation (Fire Drill or otherwise)
Notification Appliance Circuits (NACs) can be activated by pressing and
holding the DRILL button for at least two seconds.
NOTE : You may want to disconnect the municipal box by
sliding the DISCONNECT switch, located on the 4XTM
module, to its disconnect position (to the right). If a DACT is
connected, notify the monitoring service before conducting
any fire drills or tests.
Alarm Silencing
Notification Appliance Circuits may be silenced by pressing the ALARM
SILENCE button. ALARM SILENCED will turn on yellow. Subsequent
alarms will reactivate circuits. Press the RESET button to clear the
"silenced" condition.
NOTE: Notification Appliance Circuits may be programmed
as nonsilenceable. Also, Signal Silence Inhibit, if enabled, will
prevent silencing of NACs for five minutes after an alarm (see
manual).
To test the indicators, LCD display and piezo
Press and release the RESET button and check all indicators/LEDs.
Every indicator/LED should be on, LCD shows all pixels on, piezo
sounder beeps.
For more information, refer to the NFW-100X Series Manual, Document
#LS10131-001NF-E. It is kept in the following location:
_______________________________________________________
THIS SHEET SHALL BE FRAMED ADJACENT TO THE
CONTROL PANEL
Document #LS10132-001NF-E
Rev. B
7/25/2018
ECN 18-323