Read Status
The operator selects the type of device which is to be viewed by pressing 1 for Detector or 2 for Module. If 1 is pressed, the display will
change to the following screen:
Entering the three digit detector address will cause the control panel to display the current status of the selected device. For example, if a
detector with address 001 on the SLC loop is entered, a display similar to the following will appear:
The information in the preceding display includes:
NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)
SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be ION for ionization smoke detector)
NORTH CLASSROOM - the Adjective/Noun label for this device
Z005 - the first of five possible assigned software zones
1D001 - 1 = SLC Loop, D = Detector, 001 = Address 001
V - Alarm Verification Enabled (V = Yes, * = No)
S - Silenceable for control modules (S = Yes, * = No)
W - Walktestable for control and monitor modules (W = Yes, * = No)
Pressing the down arrow key, while viewing the screen shown above, will allow the operator to view additional programming informa-
tion about the selected device, such as:
Enable/Disable Status
Device Type
Alarm Verification On/Off (for detectors)
Walktest Yes/No
PAS (Positive Alarm Sequence) Yes/No (for detectors only)
Pre-Signal Yes/No (for detectors and monitor modules)
Zone Assignments (five maximum)
Chamber Value
Adjective/Noun descriptor
Silenceable Yes/No (for control modules)
MNS Override Enabled/Disabled (for control modules)
Wireless Yes/No (for detectors only)
Sounder Base Yes/No (for detectors only)
Sounder Base Values and Zone Assignments (for detectors only)
4.24.2 Zones
READ STATUS
1=SYSTEM POINT
2=ZONES
Read Status Screen #1
From the preceding screens, the control panel operator can view:
Zones Installed - all software zones programmed into the system (99 maximum)
Zones Enabled - all software zones that are enabled
Zones Disabled - all software zones that have been disabled
Special Purpose - on or off programming for Special Purpose Zones 97 reserved for PAS, 98 reserved for Pre-signal, 99 reserved for
Two Stage, and 96 for Local Alarm
Zone Type - the Type assigned to each installed zone (default is Alarm)
Zone Message - the Message assigned to each installed zone
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
READ SYSTEM POINT
ENTER DETECTOR#

NORMAL SMOKE(PHOTO)
NORTH CLASSROOM
Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed:
ZONES
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zones Screen #1
Z005
V
1D001
ZONES
1=SPECIAL PURPOSE
2=ZONE TYPE
3=ZONE MESSAGE
Zones Screen #2