Module Start-up

Power-Up Time

The CPE115 requires at a minimum 35 to 40 seconds to complete power-up. When
power is applied, all the Ethernet Port LEDs blink once. When power up is complete,
the OK LED turns on and remains steady whereas the RUN LED indicates the current
run mode.
Whenever the internal super capacitors are completely
discharged, the CPE100 might take approximately 105 seconds
to complete the power-up sequence. Typically, this occurs when
the unit is without power for a few days.
You Will Need:
This PACSystems standalone controller RSTi-EP CPE115.
An external power supply 9-30 VDC provided by a Class II power
supply marked as "double insulated", Limited Power Source (LPS),
or a SELV source with a minimum 32 VDC listed fuse with 3 A max
rating is required to power the CPE115.
A mating connector for the power input terminal block (Figure
10) is shipped with the unit. This mating connector accepts
flexible copper wire sizes 22 to 16 AWG. Screw torque: 2 in-Ib. Temperature
rating for copper wire: 80°C. Wiring should be stripped prior to connecting to the
mating connector and cannot exceed 30 m in length.
A DIN rail, typically mounted in an enclosure, as discussed above. Alternately,
mount the unit using the (optional) panel-mount compatible adaptor.
A computer running PAC Machine Edition (PME) configuration and
programming software. PME Version 9.50 & SIM 1 or later.
15
PACSystems™ RSTi-EP EPSCPE115 Standalone CPU Quick Start Guide
Figure 10:
CPE115 Power
Connector &
Pinout
GFK-3039C