Installation & Mounting
As shipped, the CPE115 is intended for mounting on a DIN rail. An optional panel-
mount adaptor is also available (part number: ICMFAACC001-AA). If panel-
mounting is required, replace the DIN-rail adaptor with the panel-mount adaptor
using the screws supplied with that adaptor. Both adaptors attach to the rear of the
CPE115 chassis using four M3 screws. Torque newly-installed screws to 5.3 in-Ibs
(0.6 Nm) when installing a new adaptor plate.
As shipped, the CPE100 is intended for mounting on a DIN rail. An optional panel-
mount adaptor is also available (part number: ICMFAACC001-AA). If panel-
mounting is required, replace the DIN-rail adaptor with the panel-mount adaptor
using the screws supplied with that adaptor. Both adaptors attach to the rear of the
CPE100 chassis using four M3 screws. Torque newly-installed screws to 5.3 in-Ibs
(0.6 Nm) when installing a new adaptor plate.
CPE115 is considered open equipment (having live electrical parts that may be
accessible to users) that may only be installed and operated in lockable housings,
cabinets, or electrical operations rooms. Only trained and authorized personnel may
access the equipment.
For applications requiring functional safety or in order to maintain compliance with
the ATEX Directive [Class 1, Zone 2 area (Category 3)], the surrounding housing
must meet at least IP 54.
For installation in marine applications where compliance with the marine Type
Approval must be maintained, then the CPE115 must be installed within an RF-
shielded enclosure.
Thermal Requirements
When mounting the CPE115, allow a minimum clearance of 50mm on the left & right
side of the unit and a minimum clearance of 100mm on the top & bottom sides.