M-NET wiring
(1) Use 2-core × 1.25mm² shield wire for electric wires.
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block. Connect one core of the transmission
wire (non-polar) to A terminal and the other to B. Peel the shield wire, twist the shield
part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal (A, B,
S) on M-NET terminal block should be individually wired to the other outdoor unit's
terminal, i.e. A to A, B to B and S to S. In this case, choose one of those outdoor units and drive a screw to fix an earth
wire on the plate as shown on the right figure.

8-4-1. M-NET address setting

In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to CITY MULTI
system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the
setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as
that of the indoor unit in CITY MULTI system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches
(SW11 for 10s digit and SW12 for 1s digit), which
is located on the M-NET board of outdoor unit.
(Initial setting: all addresses are set to "0".)

8-4-2. Refrigerant address setting

In the case of multiple grouping system (multiple refrigerant circuits in 1 group), indoor units should be connected by remote
controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to "00" if the group set-
ting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Initial setting: all
switches are OFF. (All refrigerant addresses are "00".)]
Refrigerant
address

8-4-3. Regulations in address settings

In the case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above
section. Set the lowest number in the group for the outdoor unit whose refrigerant address is "00" as its M-NET address.
Centralized
controller
Power
supply unit
Refrigerant addresses can be overlapped if they are in the different group.
Centralized
controller
Power
supply unit
Note: In group B, M-NET address of the outdoor unit whose refrigerant address is "00" is not set to the minimum in the group.
As "3" is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address
in the group for the outdoor unit whose refrigerant address is "00".
OCH738
<Setting example>
ON
ON
ON
OFF
OFF
OFF
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
0
1
2
ON
ON
ON
OFF
OFF
OFF
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
8
9
10
Group A
Refrigerant
Refrigerant
address 00
address 00
M-NET
M-NET
address 01
address 02
A-control
A-control
remote
remote
controller
controller
Group A
Refrigerant
Refrigerant
address 00
address 01
M-NET
M-NET
address 01
address 02
A-control
remote
controller
23
M-NET Address No.
SW11
10s
Switch
digit
setting
SW12
1s
digit
ON
ON
ON
OFF
OFF
OFF
1 2 3 4 5 6
1 2 3 4 5 6
3
4
ON
ON
ON
OFF
OFF
OFF
1 2 3 4 5 6
1 2 3 4 5 6
11
12
Group B
Refrigerant
address 01
M-NET
address 03
TB5
Group B
Refrigerant
address 00
M-NET
address 04
TB5
A-control
remote
controller
M-NET
terminal
Earth
block
wire
A
B
S
Transmission
Shield
wire
part
1
2
50
ON
ON
OFF
OFF
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
5
6
7
ON
ON
OFF
OFF
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
13
14
15
Group C
Refrigerant
address 00
M-NET
address 04
A-control
remote
controller
Refrigerant
Refrigerant
address 01
address 02
M-NET
M-NET
address 03
address 05

Hide quick links: