Troubleshooting — General
1. Low Level Alarm
Check controller emergency stop
Check that manual inlet valves are open
Check that remote fuel supply pump is operating properly
Check that inlet solenoid valve is energized. If not check for loose wires or fuse issue.
Check that level sensor pump start signal is active on controller.
Check inlet strainer for debris.
Check main tank fuel levels
Check PLC normal operating status.
2. High Level
Check that the inlet solenoid valve is de-energized
Check that the level sensor pump stop signal is energized
Check the solenoid valve for leakage
3. High Level Return Flow Pump does not start:
Check power to motor starters and controllers,
check emergency stop,
check motor overloads
4. High Level Return Flow Pump Low Flow rate:
Check discharge piping between pump and main tank
Check pump prime and tightness of suction side connections.