2.3.1 Power ............... 3 2.3.2 Trip..............3 Specifications are subject to change without notice. 2.3.3 CT Verification..........3 Startco Engineering Ltd. is not liable for contingent or Analog Output............. 3 consequential damages, or for expenses sustained as a Self Diagnostics ............3 result of incorrect application, incorrect adjustment, or a malfunction.
Page 4
Startco Engineering Ltd. Page ii SE-704 Earth-Leakage Monitor Rev. 0 This page intentionally left blank. Pub. SE-704-M, January 18, 2008.
RESET switch safe mode, non-volatile memory retains the trip status of is pressed or the remote-reset terminals (6 and 7) are the SE-704. If tripped, and the supply voltage is cycled, momentarily connected. In the non-fail-safe relay...
3. OVERALL DIMENSION WHEN MOUNTED ON DIN EN50022 35 mm x 7.5 mm TOP-HAT RAIL. 4. ADJUSTMENT KNOBS ARE REMOVABLE. 5. CONFIGURATION SWITCHES SHOWN BOTTOM IN DEFAULT POSITION. FIGURE 1. SE-704 Outline and Mounting Details. Pub. SE-704-M, January 18, 2008.
SE-704 earth-leakage monitor and an SE-CS30 current supply voltage. sensor connected as shown in Fig. 2. An SE-704 can be surface or DIN-rail mounted. See 2.3.2 T Fig. 1. Panel mounting requires a PMA-55 or PMA-60 The red LED labeled TRIP indicates a trip. A solid red Panel-Mount Adapter.
SE-704 Earth-Leakage Monitor Rev. 2 4. SE-704 C OMPATIBILITY The current SE-704 has been enhanced with the addition of non-volatile trip memory for the fail-safe relay operating mode. Prior to hardware revision 01, a mechanical flag was used instead of non-volatile trip memory.
(2.07) FRONT SIDE NOTES: MOUNTING FOOT INSTALLATION DIMENSIONS IN MILLIMETRES (INCHES). TOOL PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED (DETAIL ‘A’) MOUNTING SCREWS: M4 OR 8-32. DETAIL ‘A’ FIGURE 3. SE-CS30-26 Current Sensor. Pub. SE-704-M, January 18, 2008.
(0.22) FRONT SIDE NOTES: MOUNTING FOOT DIMENSIONS IN MILLIMETRES (INCHES). INSTALLATION TOOL PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED (DETAIL ‘A’) MOUNTING SCREWS: M4 OR 8-32. DETAIL ‘A’ FIGURE 4. SE-CS30-70 Current Sensor. Pub. SE-704-M, January 18, 2008.
Startco Engineering Ltd. will (at Startco’s option) Radiators repair, replace, or refund the original purchase price of an SE-704 that is determined by Startco to be defective if Certification ......CSA (Canada and USA) it is returned to the Startco factory, freight prepaid, within the warranty period.
10% of the SE-400 setting. Set the test current to 120% of the SE-704 setting. Inject the test current through the current-sensor window for at least 2.5 seconds. Verify that the circuit under test has reacted properly.
Page 16
Startco Engineering Ltd. Page 12 SE-704 Earth-Leakage Monitor Rev. 0 This page intentionally left blank. Pub. SE-704-M, January 18, 2008.