Battery System Connections; Table B-1 Recommended Master Ground Bar Lugs; Table B-2 Recommended Junction Panel Ground Lugs - Motorola iDEN Site Controller System Manual

Gen 3
Table of Contents

Advertisement

Appendix B Parts & Suppliers

Battery system connections

B-10
Selecting master ground bar lugs
Table B-1 identifies recommended part numbers for wire lugs used to
connect chassis ground wiring to the master ground bar from each cabinet.
Table B-1
Recommended master ground bar lugs
Wire size
Wire type
#2 AWG
stranded
#2 AWG
stranded
#6 AWG
stranded
#6 AWG
stranded
These lugs require the use of the TBM5-S crimping tool.
NOTE:
† All part numbers are Thomas & Betts.
Selecting cabinet ground lugs
Table B-2 identifies recommended part numbers for wire lugs used to
connect chassis ground wiring to the grounding point of each cabinet.
Table B-2
Recommended Junction Panel ground lugs
Wire size
Wire type
#2 AWG
stranded
#6 AWG
stranded
These lugs require the use of the TBM5-S crimping tool.
NOTE:
† All part numbers are Thomas & Betts.
The cable loop length refers to the total length of wire within a given circuit.
For example, the combined length of the -48 Vdc (hot) lead and the DC
return lead equals the cable loop length. This means that a cabinet that needs
16 feet of wire between the batteries and Power Supply Rack has a total loop
length of 32 feet.
Gen 3 Site Controller System Manual
Lug
color
Description
brown
single 1/4" diameter hole
brown
double 1/4" diameter hole, 5/8"
center
blue
single 1/4" diameter hole
blue
double 1/4" diameter hole, 5/8"
center
Lug
color
Description
brown
single 1/2" diameter hole
blue
single 3/8" diameter hole
P/N †
54107
54207
54105
54205
P/N †
54145
E6-12
68P80801E30-A 5/1/2002