Yoshitake GD-200 Series Manual page 7

Pressure reducing valve
Table of Contents

Advertisement

< For Air > 
   
Fig.7 
Example of Selection 
When the inlet pressure (P
) is 0.5 MPa, the reduced pressure (P
) is 0.3 MPa and the 
1
2
3
flow  rate  is  800Nm
/h,  for  instance,  the  size  of  the  pressure  reducing  valve  is  selected 
as follows. Find the intersection point (A) of the inlet pressure (P
) 0.5 MPa and 
1
reduced pressure (P
) 0.3 MPa and go straight down from the point (A) to find the 
2
intersection (B) crossing the flow rate line. The point (B) is between line of 32A 
and 40A,and choose larger size 40A for application. 
-6-