Assistance In The Event Of Malfunction - Honeywell ECOMAX Operating Instructions Manual

Self-recuperative burner
Hide thumbs Also See for ECOMAX:
Table of Contents

Advertisement

7
8
Installing the gas insert
CAUTION
ECOMAX
®
..C: do not strike the mixing funnel
against the ceramic air guide tube. Risk of breakage.
ECOMAX
®
..M: the gas insert must be slid into the
air guide tube with no resistance. External forces
10
11
may damage the ceramic combustion chamber.
▷ ECOMAX
®
..M, ECOMAX
sizes 1 – 3: install the combustion chamber us-
ing ceramic retaining bolts. During installation,
ensure that the retaining bolts do not fall out.
42
1
3
4
▷ Tighten the nuts in two cycles in a crosswise
fashion. Torque for ECOMAX
ECOMAX
®
 4 – 5: 35 Nm.
6 Connect the grounding cable.
7 Connect the gas line to the gas insert.
8 Connect voltage to the system.
9 Open the gas and air supply.
0 Check for tightness, see page 10 (Leak test).
 Start the burner, see page  9 (Commission-
ing).
DANGER
Risk of explosion and poisoning in case of
burner adjustment with an air deficiency! Ad-
just the gas and air supply so that the burner is
always operated with excess air – otherwise CO
will form in the furnace chamber. CO is odourless
and poisonous! Conduct a flue gas analysis.
 Produce a maintenance report.
9
®
..F and ECOMAX
®
..P,
Check the
retaining bolts
as they are
only inserted
loosely.
2
5
®
 0 – 3: 18 Nm,
GB-15
Assistance in the event of
malfunction
DANGER
Electric shocks can be fatal! Before working on
possible live components, ensure the unit is discon-
nected from the power supply.
Risk of injury! Burner heads have sharp edges.
Fault-clearance must only be undertaken by author-
ized trained personnel.
▷ If no fault is detected when checking the burner,
proceed to the automatic burner control unit and
check for faults in accordance with the relevant
operating instructions.
? Faults
! Cause
• Remedy
? Burner does not function?
! Valves do not open.
• Check the voltage supply and wiring.
! Gas inlet pressure is too low.
• Check the filter for dirt.
• Check the gas supply.
! Air inlet pressure is too low.
• Check the fan and air supply.
! Gas and air pressures on the burner are too low.
• Check the restrictors.
• Check/adjust the start rate setting, see operating
instructions for solenoid valve.
! Automatic burner control unit does not function
correctly.
• Check the device fuse.
• Note the automatic burner control unit operating
instructions.
! Short-circuit of the UV sensor.
• Replace the UV sensor.
• Note the UV sensor operating instructions.
! Automatic burner control unit signals a fault.
• Check the ionization cable.
• Check the ionization current. The ionization cur-
rent must be at least 5 µA – stable signal.
• Check whether the burner is adequately ground-
ed.
• Note the automatic burner control unit operating
instructions.
! No ignition spark is created.
• Check the ignition cable.
• Check the voltage supply and wiring.