Specifications And Model Selection Guide; Introduction; Specifications - Honeywell HercuLine 10260A Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

2. Specifications and Model Selection Guide

2.1 Introduction

This chapter provides the user with the specifications and the Model Selection Guide for the 10260A Series
Actuator.

2.2 Specifications

Physical
Weight
Enclosure
Gear train
Mechanical stops
Operating Temperature
Storage Temperature
Relative Humidity
Scale
Crank Arm
Output Shaft
Rotation
Direction of Rotation
Manual Handwheel
Lubrication
Fuses
2/03
10260A Series Actuators – Installation, Operations, and Maintenance
Specification – General
40 lb. (18 kg) net
Precision machined Aluminum alloy casting, finished in light gray powder coat epoxy.
Alloy steel, high efficiency steel spur gear primary train with safety fused idler gear.
Precision ground, self locking/self releasing worm gear final mesh.
To prevent over-travel
–30 °C to +85 °C (–20 °F to +185 °F)
–40 °C to +93 °C (–40 °C to +200 °F)
Fully operable over the range of 0-99 % R.H. non-condensing
0 % to 100 % corresponding to full crank arm travel.
Adjustable radii (1-7/16" to a maximum of 5"). Position adjustable through 360°
rotation. Optional 12" crank arm adjustable 0-12" radii.
1" diameter, 1-1/2" long is standard on 10261A, 10262A, 10264A, 10266A, 10267A,
10268A.
1" diameter, 2" long is standard on 10263A, 10265A and 10269A optional on other
models.
0
90
degrees between 0 % and 100 % on scale, limited by mechanical stops.
Field selectable via switch and jumper. Default = CCW (determined looking into the
shaft)
Provides a means of positioning the actuator in the event of a power failure or set-
up.
Texaco Starplex 2 EP Grease
Bussmann GDB1.6:
Littlefuse 312001:
Specifications and Model Selection Guide
1.6 Amp Fast
1.0 Amp Fast
7

Hide quick links:

Advertisement

Table of Contents
loading