Certification
5.2 EMC and Environmental Type Tests
61000-4-6
61000-4-8
61000-4-29
61000-4-11
IEC 60255-5
a
Siemens specified severity level.
IEEE 1613 EMC Immunity Type Tests
Note
The RUGGEDCOM RMC41 meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports.
Fast Transient
24
Test
IEC
Induced (Conducted) RFI
IEC
Magnetic Field
IEC
Voltage Dips and Interrupts
IEC
Dielectric Strength
HV Impulse
Description
ESD
Radiated RFI
Description
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Enclosure
Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
Test Levels
± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
10 V
10 V
10 V
10 V
40 A/m continuous,
1000 A/m for 1 s
1000 A/m for 1 s
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
30% for 1 period,
60% for 50 periods
100% for 5 periods,
100% for 50 periods
2 kV  (Fail-Safe
Relay output)
1.5 kV
2 kV
5 kV  (Fail-Safe
Relay Output)
5 kV
5 kV
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
Installation Manual, 04/2021, C79000-G8976-1010-11
Severity
Levels
3
4
3
3
3
3
a
Note