Parameters

2.1
Parameters
Table 2-1
Parameters for analog output module
2AO U HF
Group diagnostics (parameter
assignment error, internal
error)
Diagnostics: Short circuit to M
1
Response to CPU/master
STOP
Type/range of output
Substitute value
2
1 No diagnostics detection between -0.296 V and +0.296 V
If there is no voltage being supplied to the interface module or COMPACT module but the supply to the analog output
2
modules continues, the substitute values that have been assigned parameters are output. Substitute values must be within
the nominal range. You can assign values from -27,648 to +27,648 as parameters (when assigning parameters using the
GSD file).
2AO U HF analog electronic module (6ES7135-4LB02-0AB0)
Manual, 04/2007, A5E01076940-01
Range of values
Disable
Enable
Disable
Enable
No output current or voltage
Substitute a value
Keep last value
Deactivated
1 to 5 V
±10 V
To 65,535 (value range must lie
within the nominal range)
Default setting
Disable
Disable
No output current or voltage Module
±10 V
±10 V: 0 V
±5 V: 0 V
1 to 5 V: 1 V
2
Applicability
Module
Channel
Channel
Channel
11