feed or uninterruptible power supply (UPS) must be prepared. The component
failure rate is likely to be higher when the system operates in an environment with
frequent power outages or an unstable power supply than in an environment where
the supply of power is stable.
 
Electrical work and installation must be performed in accordance with the electrical
regulations of the region, municipality, or country.
Note - If the system will be used in a region where an appropriate input power outlet is not
available, contact a certified electrician. Have the electrician remove the connectors from each
power cord and connect the power cord to a dedicated branch circuit. Check the electrical
regulations of the region about installation conditions.
2.9.1

Electrical Specifications

Table 2-8
Note - The values listed in
configuration of each chassis. The actual values vary depending on the system configuration.
Table 2-8     Electrical Specifications (SPARC M12-1)
Item
Number of power cords
Power cord length (*1)
Redundancy
Frequency
Maximum input current (*2)
Maximum power consumption
Apparent power
Rush current (*3)
Leakage current (*3)
*1 The SPARC M12-1 is pulled out to perform maintenance. Therefore, you need to consider an extra length of 1.5 m when ordering the
power cord.
*2 The current that flows through each power cord in a redundant configuration is half the value listed in
*3 The value is per power cord.
28
Fujitsu SPARC M12-1 Installation Guide ・ June 2021
and
Table 2-9
list the electrical specifications of each chassis.
Table 2-8
Specification
Input Voltage of 100 to 120 VAC
2
(1 for each PSU)
Maximum length of 3.0 m (9.8 ft.)
1+1 redundant configuration
50 Hz/60 Hz, single phase
8.1 A
785 W
809 VA
40 A peak or less
1.75 mA or less
and
Table 2-9
are based on values for the maximum
Input Voltage of 200 to 240 VAC
2
(1 for each PSU)
Maximum length of 3.0 m (9.8 ft.)
1+1 redundant configuration
50 Hz/60 Hz, single phase
4.0 A
774 W
798 VA
40 A peak or less
1.75 mA or less
Table