Connection

■Main circuit
Fig. 9-1
CAUTION
Max. 200 mm
Fig. 9-4
■Control circuit
¡Crimp-type terminal size
Recommended crimp-type terminals
2
2
Ex.1.25 mm
~ 2.0 mm
wires
N2-M3(RAP2-3.5) (JST)
FN2-M3(RBP2-3.5) (JST)
N2-YS3A(JST)
Max. 7.2 mm
Fig. 9-5
CAUTION
25mm
Use small washers to connect that
the washers do not overlap with
each other.
Fig. 9-2
Fixing support
If the screw is tightened with exces-
sive torque, the terminal and the
screw may be damaged. Tighten
the screw to the specified torque.
Screwdrivers should be used whose
diameters are of size suited to the
diameters of the cruciform grooves.
Size of toolhead : PH2
M3.5 ✕ 10
Torque: 0.8 ~ 1.2N・m
Fig. 9-6
CAUTION
M12
40 ~ 50N·m
Conductor
ACB termi-
nal (silver-
plated)
Fig. 9-3
Passage wiring
Fig. 9-7