Charging Operation - Mitsubishi Electric AE-SW Series Instruction Manual

Low-voltage air circuit breakers
Hide thumbs Also See for AE-SW Series:
Table of Contents

Advertisement

8
To drawout the breaker, pull each side equally.
Otherwise (in the case of drawing slantwise) the breaker
can not move smoothly.
When ACB is installed at a high position, please do the
Drawout / Insert operation by two people.
(Note:)
Since the center of gravity is by the terminal, the
Cradle support is required to prevent from falling.
(See Fig. 15-1)

Charging operation

< Manual charging >
Press the charging handle down at full stroke 7 or 8 times
until a click sounds. (It is completion when a charging handle
becomes light.) Then, the closing spring will be fully charged.
The charging indicator will show CHARGED.
The operating load is 30 N·m or less.
< Motor charging >
The closing spring is electrically charged.
This is an "ON charge method", in which the spring is auto-
matically charged when the breaker is closed.
¡Manual charging operation is also possible using the charg-
ing handle.
¡Although the charging motor has a short time rating it can
be continuously operated for up to ten times.
¡Since the charging complete switch is separate from the
motor charging circuit, the sequence can be arranged as
required.
8
Fig. 15-2
Table 15-1 Motor charging rating
Rated
Applicable
Applied
Inrush
voltage
voltage
voltage
current
(V)
range (V)
(V)
(peak) (A)
24 DC
18-26.4
24
48 DC
36-52.8
48
100-125
100
10 (10)
85-137.5
AC/DC
125
12 (12)
200-250
200
170-275
AC/DC
250
Note 1: Contents in parentheses show the case of AE4000-SWA 4-pole,
AE4000-SW, AE5000-SW and AE6300-SW.
24 V DC and 48 V DC products of AE4000-SWA 4-pole, AE4000-SW,
AE5000-SW and AE6300-SW cannot be manufactured.
Note 2: Operating power supply capacity of the motor charging should be
prepared not to be lower than an applicable voltage range during
charging.
MD circuit diagram
Charging
completion
413
Switch output
414
U1
Control
supply
U2
Apply for further of 24 V DC and 48 V DC.
Breaker
Fig. 15-3
Cradle support
Fig. 15-1
Charge operation: 7 to 8 times
Criterion for
Steady
Charging
power
current
requirement
time
(A)
(VA)
22
6
500
14
3
3 (4)
700
5 sec or
less
3 (4)
1000
5 (7)
1 (2)
700
6 (8)
1 (2)
1000
Charging completion switch
Charging limit
switch
M
Motor
Control
relay
Motor charging
circuit
E − 15