Table 4
.
Check Points for
Inspection
( cont
.
)
z
H
Check Point
No
.
Check Item
Check Method
Criteria
What
to
do
Remarks
m
z
8
Barrier
(
Vacuum
Interrupter
Support
)
Contamination
,
discoloration
,
and damage .
Visual check
.
There should be no
dust and
foreign
matter .
Wipe with
a clean
cloth
.
>
Z
o
m
There should be no
cracks or
damages
.
Factory
service
required if
cracked or
damaged .
9
Measurement
When the insulation
resistance between
the main
circuit is
low
,
clean the surface
of the
vacuum
interrupter with a dry
cloth and then take
measurements
again
.
of
Measuring
location
Insulation
resistance
Megger
Insulation
Resistance
Main Circuit
-
Ground
500 Mohm
or
more
1000 V
Control
Circuit
-
Ground
2 Mohm or
more
500 V
500 Mohm or
more
Between