8.4 Up/Download
Error messages
Unexpected behavior
If the download process is canceled for any reason, all parameters that have been
overwritten by the download process will remain changed. The drive may be in an unknown
state and its behavior may not be as expected. A factory reset should be performed to
ensure that the drive is in a known, safe state.
1. Incorrect type of argument
The format of the parameter in the file does not conform to the required
format.
Press OK will return the IOP-2 to the download screen.
Remedy
Edit the CLI file and correct the formatting of the parameter, in this case,
delete the "tt" and replace it with the correct parameter number then
restart the download process.
2. Parameter not written
The parameter could not be written to the drive because the parameter
was not set to the correct value or range of the index.
The user has three options:
Try again: The IOP-2 will attempt to write the parameter to the drive
again, but if it is a restricted parameter it will fail again. If successfully
written, the download process will continue until it has completed.
Skip: Ignore the parameter and do not attempt to write it to the drive.
The download will continue until it is completed.
Cancel: The download process will be canceled and the IOP-2 will return
to the normal download screen.
3. The download of the parameters to the drive was not completed
successfully.
Press OK to return to the normal download screen.
58
WARNING
Intelligent Operating Panel 2 (IOP-2)
Operating Instructions, 06/2020, FW V2.6, A5E39549448B AH