Other Approvals

This device meets the requirements of the following additional standards:
6.2

EMC and Environmental Type Tests

The RUGGEDCOM RS900F has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests
61000-4-2
61000-4-3
61000-4-4
61000-4-5
61000-4-6
RUGGEDCOM RS900F
Installation Manual, 04/2021, C79000-G8976-1350-07
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General
Requirements
NEMA TS-2
Traffic Controller Assemblies with NTCIP Requirements
Test
IEC
ESD
IEC
Radiated RFI
IEC
Burst (Fast Transient)
IEC
Surge
IEC
Induced (Conducted) RFI
Description
Enclosure
Contact
Enclosure Air
Enclosure
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
Certification
6.1.10 Other Approvals
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
± 4 kV Line-to-Ground
± 2 kV
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
10 V
Severity
Levels
4
4
x
4
4
4
4
3
4
3
37